5311RT
RONDO SYSTEMS - TILE CEILINGS
1
GENERAL

If you have pre-customised this work section using the "questions and answers" provided as part of the downloading process, it may be necessary to amend some clauses to suit the final project-specific version.

The section must still be checked and customised to suit the project being specified, by removing any other irrelevant details and adding project-specific details and selections.

 

This section relates to the supply and installation of Rondo DONN® Exposed Grid Ceiling System, and the supply and installation of ceiling tiles.

It includes:

Modify / expand this clause to suit requirements of the final version of the section.

 

Rondo DONN® Exposed Grid Ceiling System can be used to support a wide range of ceiling tile types, refer to the separate tile Manufacturer's / supplier's for product details and to ensure compatibility with selected Rondo DONN® Exposed Grid Ceiling System.

 

Rondo Building Services Pty Ltd offer an engineering design service, delivering project specific documentation prior to consent and tender.  A detailed wind and seismic report as part of the consultant supplied information may be required in order to undertake a design.  If required a PS1 from an independent engineer can be provided for a fee, this process is facilitated by Rondo.  By contacting Rondo through the Masterspec work section support function, the design service can be coordinated with this specification section and other consultant documentation.  Rondo project specific documentation can be attached within the specification Contract Appendix.

 

The Rondo project specific documentation provides a similar level of documentation to shop drawings.  Shop drawings can be provided if the design service is not required.

 

The ceiling manufacturer/supplier will require some detailed project information to enable their specific design the ceiling system. Ensure the information is available in this specification and/or on the drawings (for instance ceiling height etc.).

Refer to AS/NZS 2785, Appendix B for typical project information requirements.

1.1
RELATED WORK

Refer to ~ for ~

Include cross references only to other work sections where they include directly related work.

 

This system is compatible with Rondo XPRESS® Drywall Grid Ceiling System.  Refer to 5313KL RONDO SYSTEMS - SHEET CEILINGS for plasterboard ceiling systems.

1.2
ABBREVIATIONS

Refer to the general section 1232 INTERPRETATION & DEFINITIONS for abbreviations and definitions used throughout the specification.

 

The following abbreviations are used throughout this part of the specification:

AWCINZ

Association of Wall and Ceiling Industries of New Zealand Inc

CAC

Ceiling attenuation class

IIC

Impact insulation class

NRC

Noise reduction coefficient

Delete abbreviations that are not used.  Add relevant abbreviations and definitions as necessary.

STC

Sound transmission class

Documents
1.3
DOCUMENTS

Refer to the general section 1233 REFERENCED DOCUMENTS.  The following documents are specifically referred to in this section:

NZBC B1/VM1

Structure general

NZBC B2/AS1

Durability

NZBC C/AS1-AS2

Protection from fire

AS/NZS 1170.0

Structural design actions - General principles

AS/NZS 1170.1

Structural design actions - Permanent, imposed and other actions

AS/NZS 1170.2: 2011

Structural design actions - Wind actions

NZS 1170.5

Structural design actions - Earthquake actions - New Zealand

AS/NZS 2785

Suspended Ceilings - Design & Installation

NZS 4219

Seismic performance of engineering systems in buildings

NZS 4541

Automatic fire sprinkler systems

AS 1397

Continuous hot-dip metallic coated steel sheet and strip - Coatings of zinc and zinc alloyed with aluminium and magnesium

Delete from the DOCUMENTS clause any document not cited.  List any additional cited documents.

 

 Note: AS/NZS 1170.2:2011 is cited in       NZBC B1/VM1 Structure at the time of writing. The new version       AS/NZS 1170.2:2021 is not yet cited. Amend the section by removing the year reference if using the 2021 version and amend the section accordingly.

1.4
MANUFACTURER/SUPPLIER DOCUMENTS

Manufacturer and supplier documents relating to this part of the work:

Rondo DONN® Exposed Grid Ceiling System Rondo brochure

Rondo Professional Design Manual

Certificate of Licence for New Zealand Made trademark - Licence No. 806965

Tracklok Seismic Bracing Guide- Partitions and Ceilings August 2021- Edition 2.

List documents relating to this part of the work, i.e. technical product/system specifications, test reports, appraisals, certification, etc. Normally they will be referred to in the text by the abbreviated title.

 

Manufacturer/supplier contact details

Company:

Rondo Building Services Pty Ltd

Web:

www.rondo.co.nz

Email:

steve.hardy@rondo.co.nz

Telephone:

09 636 5110

It is important to ensure that all personnel on site have access to accurate, up to date technical information on the many products, materials and equipment used on a project.  In most cases individual products are not used in isolation, but form part of a building process. Also a particular manufacturer and/or supplier requirements for handling, storage, preparation, installation, finishing and protection of their product can vary from what might be considered the norm.  Access to technical information can help overcome this potential problem.

Warranties
1.5
WARRANTY - MANUFACTURER/SUPPLIER

Provide a material manufacturer/supplier warranty:

10 years

For Rondo branded products against defects in materials under normal use.

In addition, Rondo warrants that the Rondo DONN® Exposed Grid Ceiling System will remain structurally sound for a period of 15 years.

 

  • Provide this warranty on the manufacturer/supplier standard form
  • Commence the warranty from the date of purchase.

 

Refer to the general section 1237 WARRANTIES for additional requirements.

Under certain conditions, a 30-year AMF/USG tile and Donn grid System Warranty can be applied for. Contact Rondo for information.

 

Modify or expand the clause to suit project or manufacturer/supplier requirements, options include:

  • Modify the form to be used
  • Commence the warranty from the date of purchase (check with the manufacturer/supplier)
Requirements
1.6
QUALIFICATIONS - GENERAL

Refer to 1270 CONSTRUCTION for requirements relating to qualifications.

Provide evidence of experience, listing completed projects of similar size and complexity.

Delete clause if using QUALIFICATIONS WORKERS - INDUSTRY QUALIFICATION REQUIREMENTS.

1.7
QUALIFICATIONS WORKERS - INDUSTRY QUALIFICATION REQUIREMENTS

Installation by a manufacturer accredited installer, using the manufacturer technical services.  Installers are to be members of the AWCINZ.  Refer to 1270 CONSTRUCTION for additional requirements relating to qualifications.

Provide evidence of experience, listing completed projects of similar size and complexity.

Delete clause if using QUALIFICATIONS - GENERAL

1.8
NO SUBSTITUTIONS

Substitutions are not permitted to any of the specified systems, components and associated products listed in this section.

1.9
SAMPLES

Refer to the general section 1270 CONSTRUCTION for details of how samples will be reviewed and how instructions to proceed will be given.  Provide the following samples for review:

 

Sample A

Sample B

Sample C

Sample description:

~

~

~

Sample type:

~

~

~

Number:

~

~

~

Location:

~

~

~

Supporting documentation:

~

~

~

Reviewer:

Contract administrator~

Contract administrator~

Contract administrator~

Time for review:

10 working days ~

10 working days ~

10 working days ~

Review criteria:

~

~

~

The intention of this clause is to allow samples to be obtained that are not otherwise readily available to a reviewer.

 

Delete rows and columns not required or add "n/a".

Sample description:

Describe the sample, size etc.

Allow to erect a sample section of the suspended ceiling system.  Subject to confirmation in writing, the sample section may form part of the completed installation.

Amend or expand this clause as appropriate to the project, including requirements for incorporating other elements - luminaires, diffusers, surrounding surfaces - into the sample section.

Sample type:

Portable sample for review

Portable control sample

Fixed sample for review

Fixed control sample

 

Control samples define requirements for type and quality and are used for comparison purposes throughout the contract.

 

A "portable" sample is a sample that is easily movable, convenient for carrying. A "fixed" sample is a sample (semi) permanently placed. Expand on these terms as necessary.

Number:

State number of samples required, e.g. a minimum of three control samples - portable allow a sample to be retained on site with the other samples retained by the contract administrator and contractor.

Location:

Identify location of fixed samples, e.g. off site, on site, in situ

Supporting documentation:

Describe any additional documents required to support the review.

Reviewer:

 

Modify to suit the project, add additional reviewers if required.

Time for review:

Alter time if required.  Expand to state timing in relation to when and where the sample is provided, e.g. at first site meeting.

Review criteria:

For example:

- Appearance

- Texture

- Colour

Add any critical items. Provide clarity for work that is not dependent on the review to continue.

1.10
RONDO SPECIFIC DESIGN DOCUMENTS

Refer to SELECTIONS for project specific design documentation by Rondo Building Services Pty Ltd, generally consisting of:

  • Design calculations
  • Dimensioned plans/elevations of elements
  • Details of construction, connections and support systems
  • Dimensions of all typical elements
  • Jointing details and method of fixing between individual elements and between this installation and adjacent work
  • Provision for thermal and seismic movement
  • Bracing requirements, due to wind and seismic loads
  • A schedule of materials, finishes and componentry

Rondo Building Services Pty Ltd offer an engineering design service, delivering project specific documentation prior to consent and tender as an alternative to the Shop Drawing process.  A detailed wind and seismic report as part of the consultant supplied information may be required in order to undertake a design.

 

By contacting Rondo through the Masterspec work section support function, the design service can be coordinated with this specification section and other consultant documentation.  Rondo project specific documentation can be attached within the specification Contract Appendix.

1.11
SHOP DRAWINGS

Refer to the general section 1235 SHOP DRAWINGS for the requirements for submission and review and the provision of final shop drawings.

 

Provide shop drawings to show the general arrangement including, but not be limited to:

  • Design calculations.
  • Fully dimensioned elevations of all elements
  • Complete details of construction, connections and all support systems
  • Dimensions of all typical elements
  • Jointing details and method of fixing between individual elements and between this installation and adjacent work
  • Provision for thermal movement
  • Provision for seismic movement and movement under prevailing wind loads
  • Bracing requirements, due to wind and seismic loads (indicate any design and construction work by others, to meet these requirements)
  • Sequence of installation
  • Co-ordination requirements with other work
  • A full schedule of materials, finishes and componentry

The general section 1235 SHOP DRAWINGS describes the process of submission and review of shop drawings.  Use this clause to describe the specific requirements of what the required shop drawings are to include.

 

Rondo Building Services Pty Ltd offer an engineering design service, delivering project specific documentation prior to consent and tender as an alternative to the Shop Drawing process.

 

By contacting Rondo through the Masterspec work section support function, the design service can be coordinated with this specification section and other consultant documentation.  Rondo project specific documentation can be attached within the specification Contract Appendix.

 

Rerun the Q&A if required to obtain the Rondo design service clause content.  Delete this clause if using the Rondo design service.

1.12
AS BUILT DOCUMENTS

Refer to the general section 1238 AS BUILT DOCUMENTATION for the requirements for submission and review of as built documents and records.

 

Provide the following as built documents and records:

~

  • Provide draft as built information prior to practical completion.
  • Provide final as built information prior to the end of the defects liability period.

The general section 1238 AS BUILT DOCUMENTATION describes the process of submission and review of as built documentation.

Use this clause to describe the specific requirements of what the required as built documents are to include.

1.13
INFORMATION FOR OPERATION AND MAINTENANCE

Refer to the general section 1239 OPERATION & MAINTENANCE for provision of the following general operation and maintenance information as electronic PDF format documents:

Supply information on the materials and method of cleaning the ceiling system over its expected life.

Use this clause to list requirements of information that is required but which does not warrant a separate specialist operation and maintenance manual.  Amend the clause if hard copy documents are required.

Compliance information
1.14
INFORMATION REQUIRED FOR CODE COMPLIANCE

Provide the following compliance documentation:

  • Manufacturer / supplier warranty.
  • Internal Rondo engineered design - refer to SELECTIONS
  • Producer Statement (PS1) - Design from supplier independent engineer.
  • Producer Statement (PS3) - Construction from the applicator / installer.
  • Producer Statement (PS4) - Construction Review from an acceptable suitably qualified person.
  • Other information required by the BCA in the Building Consent Approval documents.

Producer Statement - Design (PS1) required from consultants to be engaged by the Contractor. May involve a fee, check with supplier.

Producer Statement - Construction (PS3) required from installers as a condition of carrying out this work.

Producer Statement - Construction Review (PS4) required from consultants to be engaged by the Contractor.

A PS1 from an independent engineer can be provided for a fee.  Rondo are willing to facilitate this process.

Performance

This clause is setting a standard of performance for design by the contractor, to meet.  Specifiers should therefore consider adding some means of confirming (say by testing or certification) that the performance criteria will be or has been met.

Ensure correct information is supplied in 1220 PROJECT.

Use the following clause whether specifying by performance or not.

1.15
LOADING CODE REQUIREMENT

To AS/NZS 2785, comply with the requirements of; AS/NZS 1170.0, AS/NZS 1170.1, AS/NZS 1170.2, NZS 1170.5, NZBC B1/VM1, as appropriate.

Load combinations are considered in accordance with AS/NZS 1170.0.
In some seismic areas the connection details may not be valid.  Refer to Rondo Building Services Pty Ltd for advice.

1.16
CERTIFICATION

Provide:

  • Certificates and other evidence that the system complies with the standards of performance specified.
  • Producer Statements.
1.17
ACOUSTIC REQUIREMENTS

Use an independent testing authority to test a specimen of the ceiling system to AS/NZS 2785, 2.6 Acoustic Requirements, and submit the results for acceptance.

Refer to SELECTIONS.

Delete this clause if acoustic requirements do not apply.

1.18
FIRE HAZARD PROPERTIES

Ceiling tiles to provide a maximum Group Number to NZBC C/AS2, Table 4.3 Surface Finishes, to suit the appropriate fire risk group.

Refer to SELECTIONS.

Modify to suit project requirements and Fire Report.

Note;  Group Number to be supplied by manufacturer, or for some materials and finishes, a generic Group Number from NZBC C/AS2, Table C1.2, may be able to be used.

Delete this clause if it does not apply.

Discuss with the manufacturers before specifying.

1.19
FIRE RATING REQUIREMENT

Design the ceiling system so that together with the floor it is to NZBC C/AS1 - AS2, Appendix C, 5.1 Fire Resistance.

Refer to SELECTIONS.

Delete this clause if it does not apply - not all systems can provide a FRR.

Note here the floor system specified elsewhere.
Modify to suit project requirements.

1.20
ENVIRONMENTAL REQUIREMENTS

Durability to NZBC B2/AS1.

Design the ceiling system for use over its expected life without deterioration in the specified temperature and humidity range.  Refer to SELECTIONS.

If this clause is not used and the SITE CONDITIONS clause cannot be complied with, then allowance needs to be made for a tile that will not sag over the construction period.

1.21
REFLECTANCE

Refer to SELECTIONS.

Performance - Wind (design by contractor)

This clause is setting a standard of performance for design to be met by the contractor.  Specifiers should therefore consider adding some means of confirming (say by testing or certification) that the performance criteria will be or has been met.

Ensure correct information is supplied in 1220 PROJECT.

1.22
DESIGN PARAMETERS WIND - DESIGN BY CONTRACTOR

Design the installation to the wind pressure parameters of AS/NZS 1170.2.  Refer to general section 1220 PROJECT for general details.

Contact Rondo Building Services Pty Ltd for their internal engineering design service or to facilitate Producer Statement - Design (PS1).

Refer to SELECTIONS specific design performance requirements.

Obtain information from the project structural engineer.

Delete the clause if it does not apply and the contractor is not expected to design.

Rondo Professional Design Manual references AS/NZS 1170.2.

Performance - Seismic (design by contractor)

This clause is setting a standard of performance for design to be met by the contractor.  Specifiers should therefore consider adding some means of confirming (say by testing or certification) that the performance criteria will be or has been met.

Ensure correct information is supplied in 1220 PROJECT.

1.23
SEISMIC - SPECIFIC DESIGN

Design the system and its anchorages/fixings to resist the earthquake loads of the seismic zone in accordance with NZS 1170.5.  Refer to general section 1220 PROJECT for general details.  Contact Rondo Building Services Pty Ltd for their internal engineering design service or to facilitate Producer Statement - Design (PS1).

Refer to SELECTIONS specific design performance requirements.

Obtain information from the project structural engineer.

Delete the clause if it does not apply and the contractor is not expected to design.

Rondo Professional Design Manual references NZS 1170.5.

Quality control and assurance
1.24
INSPECTIONS

~

Use this clause for parts of the work where;

 

Special arrangements are required for notification for inspections.

These inspections may include 'Hold Points' or 'Notification Points'.

Hold Point:

Work may not proceed until the work in question has been inspected.

Notification Point:

Work may proceed, but with the Contract Administrator being given sufficient notice of this so that they can arrange to observe the work in progress, or not to observe it, as the case may be.

or

the manufacturer/supplier is required to carry out inspections outside their normal activities and provide reports or other documents in support of the work carried out.

or

the Contractor is required to carry out or engage consultants to carry out inspections of parts of the work.  It will typically be expected that the person carrying out the inspections will be required to provide producer statements in support of the work carried out.

2
PRODUCTS
Materials - Rondo DONN® Exposed Grid Ceiling System

Refer to Rondo for design assistance and advice.  This system is compatible with Rondo XPRESS® Drywall Grid Ceiling System.  Refer to 5313KL RONDO SYSTEMS - SHEET CEILINGS for plasterboard ceiling systems.

2.1
RONDO DONN® EXPOSED GRID CEILING SYSTEM

Rondo DONN® Exposed Grid Ceiling System to AS/NZS 2785.  Hot-dip galvanized steel elements to AS/NZS 2785 for carrying ceiling tiles/panels, light fixtures and air distribution elements and complying with NZS 1170.5, Section 8. Including perimeter trim, expansion joints and seismic joints/clips etc. to AS/NZS 2785.

2.2
PRIMARY SECTIONS - 24MM GRID SYSTEM

Main and cross Tees with 24mm face, double web, roll formed hot-dip galvanized steel with prepainted galvanized steel cap, available in standard and heavy duty gauges.

2.3
PRIMARY SECTIONS - 15MM GRID SYSTEM

Main and cross Tees with 15mm face, double web, roll formed hot-dip galvanized steel with prepainted galvanized steel cap, available in standard and heavy duty gauges.

2.4
RONDO WALL ANGLES

Rondo wall trim sections to AS 1397.  Steel grade and zinc coating class G2 Z275 to AS 1397.

2.5
SEISMIC RESTRAINT

To AS/NZS 2785, 4.3.3 Seismic Restraint Types and/or suitable proprietary back braces for ceiling systems.

Note: Non-structural partition walls are not recommended as seismic restraints, unless specifically designed to do so.

Components
2.6
SUSPENSION CLIPS, BRACKETS, RODS & WIRE

Refer to SELECTIONS.

2.7
SECTION JOINERS

Hot-dip galvanized steel elements manufactured from steel strip to AS 1397.

2.8
HOLD DOWN CLIPS

Refer top SELECTIONS.

As required by seismic and / or wind pressure requirements.

Accessories
2.9
FASTENERS

Pop-rivet, Tek® Screws, XDSC Clip.

Ceiling tiles

Rondo DONN® Exposed Grid Ceiling System can be used to support a wide range of ceiling tile types, refer to the separate tile Manufacturer's / supplier's for product details and to ensure compatibility with selected Rondo DONN® Exposed Grid Ceiling System.

2.10
MINERAL FIBRE TILES

Tiles manufactured from mineral fibre base board finished with a suitable durable surface.

2.11
PLASTERBOARD TILES

Gypsum plaster core encased in a durable face and backing papers.

2.12
FIBROUS PLASTER TILES

Manufacture by a member of the AWCINZ.  Cast gypsum plaster, fibreglass reinforced.

2.13
GLASS FIBRE TILES

Pressed cut high density resin bonded glass fibre faced with vinyl.

Rewrite if the surface finish is other than vinyl sheet or film.

2.14
WOOD FIBRE TILES

Pressed low density wood fibre.

2.15
LINEAR METAL

Manufactured by a member of the AWCINZ.  Hot-dip galvanized steel or aluminium pans finished with a durable polyester finish.

Rewrite for other tile finishes.

2.16
OPEN CELL

Manufactured by a member of the AWCINZ.  Hot-dip galvanized steel strip grid with a pre-painted coating.

Rewrite for other ceiling materials such as plastic.

3
EXECUTION
Conditions
3.1
DELIVERY, STORAGE & HANDLING OF PRODUCTS

Refer to 1270 CONSTRUCTION for requirements relating to delivery, storage and handling of products.

Use this standard generic clause and if appropriate add additional special requirements.

3.2
ROUTINE MATTERS

Refer to 1250 TEMPORARY WORKS & SERVICES for protection requirements.

Refer to 1270 CONSTRUCTION for requirements relating to defective or damaged work, removal of protection and cleaning.

Use this standard generic clause and if appropriate add additional special requirements.

3.3
CO-ORDINATE SERVICES

Co-ordinate and co-operate with electrical and mechanical work to avoid conflict between suspension members and luminaires, diffusers, pipework and ducting. Confirm the provision of extra hangers and fixings.

 

Ensure co-operation with work in and above the ceiling, including the marking of specific ceiling tiles below major access points to above-ceiling services. Colour coded markings to follow the standards laid down by mechanical and electrical services.

 

Services and other attachments, attached to or supported by the ceiling grid system to AS/NZS 2785, ensure that:

  • items over 7.5kg and items under 7.5kg but falling greater than 3m, require a tether to AS/NZS 2785, anchored to structure.
  • items attached to the ceiling grid must be under 10kg mass, items over 10kg cannot be attached to the grid and must be independently supported.
  • unless designed otherwise, the ceiling systems total load of services and other attachments must not exceed 3kg/m².
  • light fittings installed to AS/NZS 2785 and NZS 4219.
  • ceiling system clearances to structure and services etc. that are not attached to the ceiling system, to NZS 4219, and/or NZS 4541 for sprinklers.

Note - Although items under 10kg mass are allowed, it is recommended that 7.5kg be considered the maximum for attaching to the grid under ULS conditions.

3.4
SITE CONDITIONS

Do not begin installation until the building is closed in, fully glazed, the roof watertight, and mechanical and electrical duct work above the ceiling completed.  To AS/NZS 2785, Appendix C, site Conditions, Installation and Inspections.

If fast track construction is used, this may not be possible and tiles must be selected accordingly.

3.5
RESPONSIBILITY

Ensure that conditions are suitable for the ceiling installation.

Installation
3.6
STANDARDS AND TOLERANCES

Refer to the general section 1270 CONSTRUCTION for general requirements.

Amend this clause to describe specific standards and tolerances to be achieved in carrying out this part of the work.  Although such tolerances are typically included in standards (NZS, AS/NZS etc) in certain circumstances it is worth restating these in this clause.

3.7
INSTALLATION - GENERAL

Install the Rondo DONN® Exposed Grid Ceiling System to AS/NZS 2785, Rondo Professional Design Manual, Rondo DONN® Exposed Grid Ceiling System Rondo brochure and Rondo Building Services Pty Ltd requirements, and to NZS 4219 where services are involved.  Fix, erect and fit to finish rigid, plumb, square and true to line and face.  Hangers and bracing are not to be fixed closer than 150mm to plenum building services.  Where components required cutting on site, use metal snips, fine-toothed band or hack saws.

Install all movement joints required.

Install Ceiling tiles to AS/NZS 2785, ceiling tile manufacturer's and Rondo Building Services Pty Ltd requirements.

3.8
INSTALLATION - SPECIFIC

Refer to SELECTIONS for Rondo Building Services Pty Ltd project specific design documentation.

3.9
INSTALL SEISMIC RESTRAINTS

Install ceiling system seismic restrains and bracing as required to prevent lateral movement and resist the imposed horizontal seismic force, to AS/NZS 2785.

Main items to consider:

  • If ceiling systems abut glazing, the horizontal seismic forces generated by the ceiling can damage the glazing.
  • If large runs of ceilings are terminated at bulkheads, the horizontal seismic forces generated by the ceiling can cause separation between the ceiling and bulkhead if not properly designed.
  • If the ceiling is terminated at a partition, design the partition to enable it to accept the seismic force generated by the ceiling.
  • If the partition is terminated at the ceiling, design above the ceiling line for the seismic force generated by the partition. This is normally achieved with continued, unlined studs or Tracklok bracing system to underside of the soffit.
3.10
PENETRATIONS

To AS/NZS 2785 and NZS 4219 generally, with sprinkler systems to NZS 4219 and/or NZS 4541, and to Rondo DONN® Exposed Grid Ceiling System Rondo brochure.  Accommodate recessed light fittings, air conditioning outlets and other electrical and/or mechanical services that are fixed to or pass through the ceiling system.

Provide independent support for these as necessary.

Careful tile selection is important with plenums.

3.11
ACCESSIBILITY

Provide access to the ceiling system and the in-ceiling and above-ceiling services so that maintenance and removal of any part can be carried out without damage to the ceiling system or panels.

As full access in all areas is clearly impractical, any special requirements for clear access will need to be defined; either by description here, or on the drawings.

3.12
ISOLATE

Isolate dissimilar metals with neoprene sheeting, tape or pipe lagging.

3.13
RETURN AIR PLENUM

Encapsulate tiles to prevent release of fibres into the ceiling space, air conditioning or ventilation system.  Clip tile down to the grid to stop lifting.

While this clause is written specifically for projects where the ceiling space is being used as a plenum, it may also be modified to suit particular projects which require some degree of assurance against the release of fibres, and/or the use of panel clips.

Completion & Commissioning
3.14
COMPLETION MATTERS

Refer to 1270 CONSTRUCTION for completion requirements and if required commissioning requirements.

Use this standard generic clause and if appropriate add additional special requirements.

4
SELECTIONS

For further details on selections refer to the Rondo website listed in manufacturer/supplier contact details.

Substitutions are not permitted to the following, unless stated otherwise.

If substitutions are permitted modify the statement above, ensure the NO SUBSTITUTIONS clause from GENERAL is treated the same.

 

Select the options to suit the project and delete options not specified.

Design documentation
4.1
RONDO SPECIFIC DESIGN

Document:

~

Submitted:

~

Available:

~

Document:

Identify Rondo specific design documents

Submitted:

Building consent, tender (or both)

Available:

Specification Contract Appendix, or describe alternative.

4.2
PRODUCER STATEMENT - DESIGN

PS1:

~

Available:

~

A PS1 from an independent engineer can be provided for a fee, this process is facilitated by Rondo.

PS1:

Identify the producer statement - design (PS1)

Available:

Specification Contract Appendix, or describe alternative.

Performance requirements

Use these clauses if specifying by performance.

4.3
ACOUSTIC REQUIREMENTS

Location:

~

Noise reduction coefficient (NRC):

~ minimum

Ceiling attenuation class (CAC):

~ minimum room to room

Typical Noise Control Recommendation Table

SPACES

TYPICAL DESIGN LEVELS

Open plan office

Ceiling NRC 0.8

Office to office

Standard STC 40-45, High STC 46-50+

Office meeting room, conference rooms.

Standard STC 40-45, High STC 46-52+, Ceiling NRC meeting 0.6-0.8 - conference 0.8

Schools

Flexible STC 25-50, Rooms STC 50-60, Ceiling NRC 0.85

Apartment to apartment, house to house, hotel room to hotel room, some inter-tenancy walls

Minimum STC 55 walls and floors, High STC 65 Minimum, IIC 55 for floors, High IIC 65 (Refer to NZBC G6 for minimum code requirements)

Bedroom in house

Standard STC 40-45, High STC 46-52+

Home theatre, home garage/workshop

High STC 55-62

 

Conditions:

  • Specific project requirements may be higher or lower than the above table.
  • Type and location of noise source can affect the requirements.
  • Flanking paths, ceiling spaces, gaps, doors etc, will need appropriate treatment.
  • IIC will sometimes need to be considered for walls, structure and services.
  • Schools, refer MOE, Design Quality Learning Spaces - Acoustics.
  • Music performance spaces usually need specific design.

 

Refer to AS/NZS 2785, 2.6 for testing requirements

4.4
FIRE HAZARD PROPERTIES

Location:

~

Group Number:

~

Group Number to be supplied by manufacturer, or for some materials and finishes, a generic Group Number from NZBC C/AS2, Table C1.2, may be able to be used.

4.5
FIRE RATING REQUIREMENT

FRR (minimum)

Ceiling

Floor system

Location          

~ / ~ / ~

~

~

~

Note here if the floor system specified elsewhere.

4.6
ENVIRONMENTAL REQUIREMENTS

Temperature range:

~ °C to ~°C

Maximum relative humidity:

~ %

If this clause is not used and the SITE CONDITIONS clause cannot be complied with, then allowance needs to be made for a tile that will not sag over the construction period.

4.7
REFLECTANCE

Reflectance:

~ % minimum

For (colour):

~

If a particular tile is selected, delete this clause.

Performance - Wind (design by contractor)
4.8
DESIGN PARAMETERS WIND - DESIGN BY CONTRACTOR

Wind design and performance criteria to AS/NZS 1170.2 as follows:

 

Parameter

Value

Design wind speed (Vdes.Ø)

~ m/s

Terrain Category (Mz,cat)

~

Shield Factor (Ms)

~

Topographic multiplier (Mt)

~

Hill-shape multiplier (Mh)

~

Lee multiplier (Mlee)

~

Internal pressure coefficient (Cp,i)

~

Fill in project values, obtain information from the project structural engineer.
These values are critical to allow the Contractor to design the ceiling accurately.
Usually design for wind is only required if there are opening external windows/doors or other sources of wind pressure differential (including some roof spaces).
Ensure that all general information is available in this specification or drawings (for instance ceiling height etc.). Refer to AS/NZS 2785, Appendix B for a checklist of typical information.
Delete the clause if it does not apply and the contractor is not expected to design.

Performance - Seismic (design by contractor)
4.9
DESIGN PARAMETERS SEISMIC - DESIGN BY CONTRACTOR

Seismic design and performance criteria to NZS 1170.5 as follows:

 

Parameter

Value

Building Importance Level

~

Design Working Life

~ years

Site Sub-soil Class

~

Near Fault Factor N(T,D)

~

Part Classification Category (P1-P7)

~

Interstorey Drift - ULS

~ mm

Interstorey Drift - SLS

~ mm

Fill in project values, obtain information from the project structural engineer.

These values are critical to allow the Contractor to design the ceiling accurately.

Ensure that all general information is available in this specification or drawings (for instance ceiling height etc.). Refer to AS/NZS 2785, Appendix B for a checklist of typical information.

Delete the clause if it does not apply and the contractor is not expected to design.

Materials - Rondo DONN® Exposed Grid Ceiling System

Refer to Rondo for design assistance and advice. This system is compatible with Rondo XPRESS® Drywall Grid Ceiling System (refer to section 5313KL RONDO SYSTEMS - SHEET CEILINGS).

4.10
RONDO DONN® EXPOSED 24MM GRID CEILING SYSTEM

Location:

~

Type/Brand:

Rondo DONN® Exposed 24mm Grid Ceiling System

Grid configuration:

~

Grid colour:

~

Main Tee:

~

Cross Tee:

~

Wall angle:

~

Suspension:

~

Joiners:

~

Retention clips:

~

Access:

~ %

Grid configuration:

Refer to grid configurations & load tables

Grid colour:

White - as standard

 

Black - projects that are larger than Rondo's basic stock holding are available with additional lead time.

Main Tee:

DX1 - 38mm (h) x 24mm (face) Main Tee

 

DX1H - 38mm (h) x 24mm (face) Heavy Duty Main Tee

 

DXB - 38mm (h) x 24mm (face) Black Cap Main Tee

Cross Tee:

DX2 - 38mm (h) x 24mm (face) Cross Tee

 

DX2H - 38mm (h) x 24mm (face) Heavy Duty Cross Tee

 

DX3 - 32mm (h) x 24 (face) Cross Tee

 

DX4 - 25mm (h) x 24mm (face) Cross Tee

 

DXBM - 32mm (h) x 24mm (face) Black Cap Cross Tee

 

DXBS - 25mm (h) x 24mm (face) Black Cap Cross

Wall angle:

WADX - 22mm (h) x 19mm (w) Steel Wall Angle

 

WAH - 22mm (h) x 19mm (w) Heavy Duty Steel Wall Angle

 

WASA - 15mm (h) x 10mm (w) x 10mm (h) x 12mm (w) Shadow Line Steel Wall Angle

 

WASL - 27mm (h) x 10mm (w) x 10mm (h) x 19mm (w) Shadow Line Long Leg Steel Wall Angle

 

WAS - 42mm (h) x 26mm (w) x 22 (w) Seismic Steel Wall Channel

 

WAB - 22mm (h) x 19mm (w) Black Steel Wall Angle

 

SA12 - 40mm (h) x 40mm (w) Seismic Steel Wall Angle

Suspension:

Suspension method and position dependant on load requirements, refer to grid configuration and load tables.  Rondo does not recommend mixing of suspension systems within the ceiling grid.

Joiners:

XDSC - Splice Clip 180°

 

XD10 - Transition Clip 90°

 

XD11 - Transition Clip - Rondo DONN® to Rondo XPRESS®

 

XD16 - Main Tee Separation Joint Clip

 

XD19 - Strongback Clip

 

XD20 - DX Tee Face Sleeve

 

XD35 - Seismic Expansion Joint Clip

 

XD36 - 3 Way Off Module Connector

Retention clips:

XD17 - Seismic Clip - Grid to Wall angle

 

703 - Tile Hold-Down Clip for 10mm to 16mm Tiles

4.11
RONDO DONN® EXPOSED 15MM GRID CEILING SYSTEM

Location:

~

Type/Brand:

Rondo DONN® 15mm Exposed Grid Ceiling System

Grid configuration:

~

Grid colour:

White

Main Tee:

~

Cross Tee:

~

Wall angle:

~

Suspension:

~

Joiners:

~

Retention clips:

~

Access:

~ %

Refer to Rondo for design (including seismic design) assistance and advice. This system is compatible with Rondo XPRESS® Drywall Grid Ceiling System.

Grid configuration:

Refer to grid configurations & load tables

Main Tee:

DC1S - 38mm (h) x 15mm (face) Main Tee

 

DC1H - 38mm (h) x 15mm (face) Heavy Duty Main Tee

Cross Tee:

DC2S - 38mm (h) x 15mm (face) Cross Tee

 

DC2H - 38mm (h) x 15mm (face) Heavy Duty Cross Tee

Wall angle:

WADX - 22mm (h) x 19mm (w) Steel Wall Angle

 

WAH - 22mm (h) x 19mm (w) Heavy Duty Steel Wall Angle

 

WAL - 40mm (h) x 19mm (w) Long Leg Steel Wall Angle

 

WASA - 15mm (h) x 10mm (w) x 10mm (h) x 12mm (w) Shadow Line Steel Wall Angle

 

WASL - 27mm (h) x 10mm (w) x 10mm (h) x 19mm (w) Shadow Line Long Leg Steel Wall Angle

 

WAS - 42mm (h) x 26mm (w) x 22 (w) Seismic Steel Wall Channel

 

WAC - 22mm (h) x 14mm (w) Steel Wall Angle

 

WAB - 22mm (h) x 19mm (w) Black Steel Wall Angle

 

SA12 - 40mm (h) x 40mm (w) Seismic Steel Wall Angle

Suspension:

Suspension method and position dependant on load requirements, refer to grid configuration and load tables.  Rondo does not recommend mixing of suspension systems within the ceiling grid.

Joiners:

XDSC - Splice Clip 180°

 

XD10 - Transition Clip 90°

 

XD11 - Transition Clip - Rondo DONN® to Rondo XPRESS®

 

XD16 - Main Tee Separation Joint Clip

 

XD19 - Strongback Clip

 

XD20 - DX Tee Face Sleeve

 

XD35 - Seismic Expansion Joint Clip

 

XD36 - 3 Way Off Module Connector

Retention clips:

XD17 - Seismic Clip - Grid to Wall Angle

 

703 - Tile Hold-Down Clip for 10mm to 16mm tiles

4.12
SEISMIC RESTRAINT

Location:

~

Brand:

~ Rondo stud brace

Type:

~

Material:

~

Where seismic forces are beyond the capability of perimeter treatment, back bracing is generally required - Add to the table if needed.

Delete Brand if not a proprietary type.

Ceiling tiles

Rondo DONN® Exposed Grid Ceiling System can be used to support a wide range of ceiling tile types, refer to the separate tile Manufacturer's / supplier's for product details and to ensure compatibility with selected Rondo DONN® Exposed Grid Ceiling System.

 

Delete clauses when cross referencing to other sections.

4.13
MINERAL FIBRE TILES

Brand:

~

Type:

~

Pattern:

~

Thickness:

~mm

Size:

~mm x ~mm to suit grid

Edge profile:

~

Backing:

~

4.14
PLASTERBOARD TILES

Brand:

~

Thickness:

~mm

Size:

~mm x ~mm to suit grid

Finish:

~

Gypsum tiles can be supplied plain (unpainted or painted) or with a vinyl facing.

4.15
FIBROUS PLASTER TILES

Brand:

~

Pattern:

~

Thickness:

~mm

Size:

~mm x ~mm to suit grid

Edge profile:

~

Backing/insulation:

~

Gypsum tiles can be solid, open-backed, or incorporating a pad of fibreglass insulation.

4.16
GLASS FIBRE TILES

Brand:

~

Surface pattern:

~

Size:

~mm x ~mm to suit grid

Thickness:

~mm

Edge profile:

~

4.17
WOOD FIBRE TILES

Brand:

~

Type:

~

Pattern:

~

Thickness:

~mm

Size:

~mm x ~mm to suit grid

Edge profile:

~

Finish:

~

4.18
LINEAR METAL

Brand:

~

Metal:

~

Profile:

~

Finish/colour:

~

Closure:

~

Insulation:

~

4.19
OPEN CELL

Brand:

~

Panel size:

~mm x ~mm

Colour:

~

Spares & maintenance products
4.20
SPARES & MAINTENANCE PRODUCTS

Refer to the general section 1270 CONSTRUCTION for details of how spares and maintenance products will be handled.  Provide the following spares and maintenance products:

Item:

~

Quantity:

~

Location:

Refer to 1270 CONSTRUCTION

Location:

If a common storage location has not been nominated in 1270 CONSTRUCTION, or is not suitable for this item, then nominate a specific location or delivery instructions.

 

Deliver into a dry store at the site or elsewhere as directed and at agreed times.