5316RC
RONDO DIRECT-FIX CEILINGS - RESIDENTIAL
1
GENERAL

If you have pre-customised this work section using the "questions and answers" provided as part of the downloading process, it may be necessary to amend some clauses to suit the final project-specific version.

 

The section must still be checked and customised to suit the project being specified, by removing any other irrelevant details and adding project-specific details and selections.

 

This section relates to the manufacture, supply and installation of:

 

This section includes:

Note - the maximum ceiling drop for direct-fix ceilings is 200mm below the structural support.  Ceiling drops greater than 200mm require a suspended ceiling grid.

Modify or extend the above description to suit the project being specified.

 

Rondo Building Services Pty Ltd offer an engineering design service, delivering project specific documentation prior to consent and tender. A detailed wind and seismic report as part of the consultant supplied information may be required to undertake a design.

If required a PS1 from an independent engineer can be provided for a fee, this process is facilitated by Rondo. By contacting Rondo through the Masterspec work section support function, the design service can be coordinated with this specification section and other consultant documentation. Rondo project specific documentation can be attached within the specification Contract Appendix.

 

Rondo project specific documentation provides a similar level of documentation to Shop Drawings. Shop Drawings can be provided if the design service in not required.

To enable the manufacturer/supplier to specifically design the ceiling system, ensure sufficient information is available in this specification and/or on the drawings (for instance ceiling height etc.). Refer to AS/NZS 2785, Appendix B for a list of typical project information.

 

This section refers to a concealed direct fixed furring channel (or batten) system supporting screw-fixed flush-finished plasterboard or other sheet material.

 

Modify the relevant clauses to suit project requirements.

1.1
RELATED WORK

Refer to 5113 PLASTERBOARD LININGS for ceiling lining.

Include cross references only to other work sections where they include directly related work, including:

An appropriate ceiling lining section(s), other than 5113 PLASTERBOARD LININGS (delete if not required).

The appropriate insulation section(s) for thermal and/or acoustic insulation.

1.2
ABBREVIATIONS AND DEFINITIONS

Refer to the general section 1232 INTERPRETATION & DEFINITIONS for abbreviations and definitions used throughout the specification.

 

The following abbreviations apply specifically to this section:

AWCINZ

Association of Wall and Ceiling Industries of New Zealand Inc

~

~

Refer to general section 1232 INTERPRETATION & DEFINITIONS for abbreviations used throughout the specification.

Documents
1.3
DOCUMENTS

Refer to the general section 1233 REFERENCED DOCUMENTS. The following documents are specifically referred to in this section:

NZBC B1/VM1

Structure general

NZBC B2/AS1

Durability

NZBC C/AS1-AS2

Protection from fire

AS/NZS 1170.0

Structural design actions - General principles

AS/NZS 1170.1

Structural design actions - Part 1: Permanent, imposed and other actions

AS/NZS 1170.2: 2011

Structural design actions - Wind actions

NZS 1170.5

Structural design actions - Earthquake actions - New Zealand

AS/NZS 2785

Suspended ceilings - Design and Installation

NZS 4219

Seismic performance of engineering systems in buildings

NZS 4541

Automatic fire sprinkler systems

AS 1397

Continuous hot-dipped metallic coated steel sheet and strip - Coating of zinc and zinc alloyed with aluminium and magnesium.

Delete from the DOCUMENTS clause any document not cited. List any additional cited documents.

 

 Note: AS/NZS 1170.2:2011 is cited in       NZBC B1/VM1 Structure at the time of writing. The new version       AS/NZS 1170.2:2021 is not yet cited. Amend the section by removing the year reference if using the 2021 version and amend the section accordingly.

 

The following are related documents and if referred to in the work section need to be added to the list of DOCUMENTS.

BRANZ BU 369

Fitting tolerances

1.4
MANUFACTURER/SUPPLIER DOCUMENTS

Manufacturer and supplier documents relating to this part of the work:
Rondo KEY-LOCK® design manual
Rondo KEY-LOCK® installation guide
Rondo KEY-LOCK® online Seismic Wizard

Rondo SCREWFIX® design manual

Rondo SCREWFIX® installation guide

Rondo SCREWFIX® online Seismic Wizard

Rondo XPRESS® design manual

Rondo XPRESS® installation guide

Rondo XPRESS® online Seismic Wizard

Rondo PANTHER® access panel design manual
Rondo PANTHER® access panel installation guide
Certificate of Licence for New Zealand Made trademark - Licence No. 806965

List documents relating to this part of the work, i.e. technical product/system specifications, test reports, appraisals, certification, etc. Normally they will be referred to in the text by the abbreviated title.

 

Manufacturer/supplier contact details

Company:

Rondo Building Services Pty Ltd

Web:

www.rondo.co.nz

Email:

steve.hardy@rondo.co.nz

Telephone:

09 636 5110

It is important to ensure that all personnel on site have access to accurate, up to date technical information on the many products, materials and equipment used on a project.  In most cases individual products are not used in isolation, but form part of a building process. Also a particular manufacturer and/or supplier requirements for handling, storage, preparation, installation, finishing and protection of their product can vary from what might be considered the norm. Access to technical information can help overcome this potential problem.

1.5
WARRANTY - MANUFACTURER/SUPPLIER

Provide a material manufacturer/supplier warranty:

10 years

For Rondo branded products against defects in materials under normal use.

15 years

In addition, Rondo warrants that the Rondo KEY-LOCK® direct-fix, Rondo SCREWFIX DF®, Rondo XPRESS® systems will remain structurally sound.

 

  • Provide this warranty on the manufacturer/supplier standard form (if not available then use the standard form in the general section 1237WA WARRANTY AGREEMENT)
  • Commence the warranty from the date of practical completion of the contract works.

 

Refer to the general section 1237 WARRANTIES for additional requirements.

~ years to ~ years are the sort of warranty periods that can be expected depending on material selection and project conditions.  Check with the manufacturer/supplier for their specific periods.

 

Modify or expand the clause to suit project or manufacturer/supplier requirements, options include:

  • Modify the form to be used
  • Commence the warranty from the date of purchase (check with the manufacturer/supplier)
1.6
WARRANTY - INSTALLER/APPLICATOR

Provide an installer/applicator warranty:

2 years

For workmanship

 

  • Provide this warranty on the installer/applicator standard form (if not available then use the standard form in the general section 1237WA WARRANTY AGREEMENT)
  • Commence the warranty from the date of practical completion of the contract works.

 

Refer to the general section 1237 WARRANTIES for additional requirements.

Modify or expand the clause to suit project or installer/applicator requirements, options include:

  • Modify the form to be used
  • Commence the warranty from the date of installation (check with the installer/applicator)
Requirements
1.7
QUALIFICATIONS - GENERALLY

Refer to 1270 CONSTRUCTION for requirements relating to qualifications.
Installers are to be members of the AWCINZ. Provide evidence of experience, listing completed projects of similar size and complexity.

Modify clause to suit project requirements

1.8
NO SUBSTITUTIONS

Substitutions are not permitted to any of the specified systems, components and associated products listed in this section.

1.9
RONDO SPECIFIC DESIGN DOCUMENTS

  Refer to SELECTIONS for project specific design documentation by Rondo Building Services Pty Ltd, generally consisting of:

  • Design calculations
  • Dimensioned plans/elevations of elements
  • Details of construction, connections and support systems
  • Dimensions of all typical elements
  • Jointing details and method of fixing between individual elements and between this installation and adjacent work.
  • Provision for thermal and seismic movement.
  • Bracing requirements, due to wind and seismic loads.
  • A schedule of materials, finishes and componentry

Rondo Building Services Pty Ltd offer an engineering design service, delivering project specific documentation prior to consent and tender as an alternative to the Shop Drawing process.  A detailed wind and seismic report as part of the consultant supplied information may be required in order to undertake a design.

 

By contacting Rondo through the Masterspec work section support function, the design service can be coordinated with this specification section and other consultant documentation.  Rondo project specific documentation can be attached within the specification Contract Appendix.

1.10
SHOP DRAWINGS

  Refer to SELECTIONS for project specific design documentation by Rondo Building Services Pty Ltd, generally consisting of:

  • Design calculations
  • Dimensioned plans/elevations of elements
  • Details of construction, connections and support systems
  • Dimensions of all typical elements
  • Jointing details and method of fixing between individual elements and between this installation and adjacent work
  • Provision for thermal and seismic movement
  • Bracing requirements, due to wind and seismic loads
  • A schedule of materials, finishes and componentry

The general section 1235 SHOP DRAWINGS describes the process of submission and review of shop drawings.  Use this clause to describe the specific requirements of what the required shop drawings are to include.

 

Rondo Building Services Pty Ltd offer an engineering design service, delivering project specific documentation prior to consent and tender as an alternative to the Shop Drawing process.

By contacting Rondo through the Masterspec work section support function, the design service can be coordinated with this specification section and other consultant documentation.  Rondo project specific documentation can be attached within the specification Contract Appendix.

Re-run the Q&A if required to obtain the Rondo design service clause content.  Delete this clause if using the Rondo design service.

Compliance information
1.11
INFORMATION REQUIRED FOR CODE COMPLIANCE

Provide the following compliance documentation:

  • Manufacturer / supplier warranty
  • Internal Rondo engineered design - Refer to SELECTIONS
  • Producer Statement (PS1) - Design from supplier independent engineer
  • Producer Statement (PS3) - Construction from the applicator / installer.
  • Producer Statement (PS4) - Construction Review from an acceptable suitably qualified person
  • Other information required by the BCA in the Building Consent Approval documents.

Producer Statement - Design (PS1) required from consultants to be engaged by the Contractor. May involve a fee, check with supplier.

A PS1 from an independent engineer can be provided for a fee.  Rondo are willing to facilitate this process.

Producer Statement - Construction (PS3) required from installers as a condition of carrying out this work.

Producer Statement - Construction Review (PS4) required from consultants to be engaged by the Contractor.

Performance

This clause is setting a standard of performance for design to be met by the contractor.

Specifiers should therefore consider adding a means of confirming (say by testing or certification) that the performance criteria will be, or has been met.

Ensure correct information is supplied in 1220 PROJECT.

Use the following clause whether specifying by performance or not.

1.12
LOADING CODE REQUIREMENT

To AS/NZS 2785, comply with the requirements of: AS/NZS 1170.0, AS/NZS 1170.1, AS/NZS 1170.2, NZS 1170.5, NZBC B1/VM1, as appropriate.

Load combinations are considered in accordance with AS/NZS 1170.0.

In some seismic areas the connection details may not be valid.

Refer to Rondo Building Services Pty Ltd for advice.

1.13
CERTIFICATION

Provide:

  • Certificates and other evidence that the system complies with the standards of performance specified.
  • Producer Statements
1.14
ENVIRONMENTAL REQUIREMENTS

To NZBC B2/AS1, Durability.
Refer to SELECTIONS

1.15
FIRE GROUP NUMBERS

The Group Number Classification to NZBC C/AS2, Table 4.3, has been determined in accordance with NZBC C/VM2 Appendix A, following testing and data reduction to ISO 5660.1.

Refer to SELECTIONS

1.16
FIRE RATING REQUIREMENT

Design the ceiling system so that together with the floor and ceiling lining system, it is to NZBC C/AS1-AS2, Appendix C, 5.1 Protection from fire.  Refer to SELECTIONS

Delete this clause if it does not apply, not all systems can provide a FRR.

Note here the floor system and ceiling lining are specified elsewhere.

Modify clause to suit project requirements.

Performance - Wind (design by contractor)

This clause is setting a standard of performance for design by the contractor, to meet.  Specifiers should therefore consider adding means of confirmation (say by testing or certification) that the performance criteria will be or has been met.

Ensure correct information is supplied in 1220 PROJECT.

1.17
DESIGN PARAMETERS WIND - DESIGN BY CONTRACTOR

Design the installation to the wind pressure parameters of AS/NZS 1170.2.  Refer to general section 1220 PROJECT for general details.

Contact Rondo Building Services Pty Ltd for their internal engineering design service or to facilitate Producer Statement - Design (PS1).

Refer to SELECTIONS specific design performance requirements.

Obtain information from the project structural engineer.

Delete the clause if it does not apply and the contractor is not expected to design.

Rondo Professional Design Manual references AS/NZS 1170.2.

Performance - Seismic (design by contractor)

This clause is setting a standard of performance for design to be met by the contractor.  Specifiers should therefore consider adding a means of confirming (say by testing or certification) that the performance criteria will be, or has been met.  Ensure correct information is supplied in 1220 PROJECT.

1.18
SEISMIC - SPECIFIC DESIGN

Design the system and its anchorages/fixings to resist the earthquake loads of the seismic zone in accordance with NZS 1170.5.  Refer to general section 1220 PROJECT for general details.  Contact Rondo Building Services Pty Ltd for their internal engineering design service or to facilitate Producer Statement - Design (PS1).

Refer to SELECTIONS specific design performance requirements.

Obtain information from the project structural engineer.  Delete the clause if it does not apply and the contractor is not expected to design. Rondo Professional Design Manual references NZS 1170.5.

Quality control and assurance
1.19
INSPECTIONS

~

~

Use this clause for parts of the work where:

 

Special arrangements are required for notification for inspections.
These inspections may include 'Hold Points' or 'Notification Points'.

  • Hold Point:  Work may not proceed until the work in question has been inspected.
  • Notification Point:  Work may proceed, but with the Contract Administrator being given sufficient notice of this so that they can arrange to observe the work in progress, or not to observe it, as the case may be.

or
The manufacturer/supplier is required to carry out inspections outside their normal activities and provide reports or other documents in support of the work carried out.
or
The Contractor is required to carry out or engage consultants to carry out inspections of parts of the work.  It will typically be expected that the person carrying out the inspections will be required to provide producer statements in support of the work carried out.

2
PRODUCTS

Select the proprietary system to suit the brief. Use the PRODUCTS clauses to get the required fire rating and acoustic control. Use the EXECUTION clauses required for the selected system. Use the SELECTIONS clauses for specific selections - brand, module, finish etc.

2.1
RONDO KEY-LOCK® DIRECT-FIX CEILING SYSTEM

KEY-LOCK® direct fix system designed to AS/NZS 2785, and Rondo KEY-LOCK® design manual.  Primary (Top Cross Rail), secondary components (Furring Channel), furring channels, battens, and snap in sections all hot-dipped (Z275) galvanized steel to AS 1397, manufactured from G2 BlueScope base metal.

Provide diagonal bracing for lateral stability where required.  Perimeter trim, expansion joints and seismic joints etc. to AS/NZS 2785.

Refer to SELECTIONS.

A direct-fix ceiling system is located within 200mm of the support structure, and is generally directly fixed to the structural support by rigid connections/brackets.

Rondo KEY-LOCK® comprises a system of furring channels or battens clipped into Direct-Fix Clips that are fitted to a structural support. Direct-Fix clips are suitable for most types of structure (typically timber joist or concrete floor slab). A standard Furring Channel Track is generally used as a perimeter trim to support edges of ceiling linings, and as a bulkhead transition.

KEY-LOCK® is suitable for Non Fire-Rated, Fire-Rated, and Acoustic design applications.

Refer to Rondo for design assistance and advice.

2.2
SCREWFIX® CONCEALED CEILING SYSTEM

SCREWFIX® direct-fix system designed to AS/NZS 2785, and Rondo SCREWFIX® design manual. Primary support ("C" channel), secondary components (furring channel), all hot-dipped (Z275) galvanized steel to AS 1397, manufactured from G2 BlueScope base metal.

Provide diagonal bracing for lateral stability where required.  Perimeter trim, expansion joints and seismic joints etc. to AS/NZS 2785.

Refer to SELECTIONS.

A direct-fix ceiling system is located within 200mm of the supporting structure, is directly fixed to the structural support by rigid connections/brackets.

Rondo SCREWFIX® offers a system of "C" channel and furring channel, allowing for a range of spans for fixings or cleats.

Suitable for supporting screw-fixed board linings e.g. plasterboard, fibrous plaster, and fibre cement.

SCREWFIX® is suitable for Non Fire-Rated, Fire-Rated, and Acoustic design applications.

Refer to Rondo for design assistance and advice.

2.3
XPRESS® DRYWALL GRID CEILING SYSTEM

XPRESS® drywall system designed to AS/NZS 2785, and Rondo XPRESS® design manual. Primary support (Main Tees), and secondary support (Cross Tees, wall trims, and clips), all hot-dipped (Z275) galvanized steel to AS 1397, manufactured from G2 BlueScope base metal.

Provide diagonal bracing for lateral stability where required.  Perimeter trim, expansion joints and seismic joints etc. to AS/NZS 2785.

Refer to SELECTIONS.

A direct-fix ceiling system is located within 200mm of the support structure, is directly fixed to the structural support by rigid connections/brackets.

Rondo XPRESS® is a light-weight concealed ceiling grid comprising of Main Tee sections and Cross Tees clipped together using Rondo QRC Clip Technology. XPRESS® is suitable for supporting board ceiling linings e.g. plasterboard, fibrous plaster, and fibre cement linings, for flush ceiling finish. XPRESS® can transition with bulkheads and other ceiling systems, and also be integrated with Rondo Exposed Grid Ceiling Systems. A variety of gypsum panels can also be supported and can be integrated with Rondo DONN® Exposed Grid Ceiling System.

XPRESS® is suitable for Non Fire-Rated, Fire-Rated, and Acoustic design applications.

Refer to Rondo for design assistance and advice.

Components

Refer to Rondo for design assistance and advice.

2.4
RONDO DIRECT-FIX BRACKETS

Rondo Direct-Fix Brackets manufactured from G2 BlueScope Steel, hot-dipped galvanized (Z275), to AS 1397.
Refer to SELECTIONS

G2 refers to a steel grade designation under formability grades, Z275 refers to a zinc coating class with a coating mass of 275g/m².  A range of clips are available to suit ceiling drop, and type of structural support the clip is fixed to (e.g. timber of concrete).

2.5
RONDO PRIMARY AND SECONDARY SUPPORT MEMBERS

Rondo primary and secondary support members manufactured from G2 BlueScope Steel, hot-dipped galvanized (Z275) to AS 1397.

Refer to SELECTIONS

G2 refers to a steel grade designation under formability grades, Z275 refers to a zinc coating class with a coating mass of 275g/m².

2.6
SECTION JOINERS

Rondo section joiners manufactured from G2 BlueScope Steel, hot-dipped galvanized (Z275) to AS 1397.
Refer to SELECTIONS

G2 refers to a steel grade designation under formability grades, Z275 refers to a zinc coating class with a coating mass of 275g/m².

2.7
EXPANSION JOINTS

Flexible backing strip by others, and EXANGLE Plaster Stopping Bead, to Rondo XPRESS® technical brochure

Rondo XPRESS® - Non-Fire Rated

2.8
CONTROL JOINTS

to Rondo XPRESS® technical brochure

Rondo XPRESS® - Non-Fire Rated

2.9
RONDO WALL TRIM

Rondo wall trim sections manufactured from G2 BlueScope Steel, hot-dipped galvanized (Z275) to AS 1397.

G2 refers to a steel grade designation under formability grades, Z275 refers to a zinc coating class with a coating mass of 275g/m².

Accessories

Refer to Rondo for design assistance and advice.

2.10
ACCESS PANEL

PANTHER® range of access panels.
Refer to SELECTIONS

3
EXECUTION
Conditions
3.1
DELIVERY, STORAGE & HANDLING OF PRODUCTS

Refer to 1270 CONSTRUCTION for requirements relating to delivery, storage and handling of products.

Use this standard generic clause and if appropriate add additional special requirements.

3.2
ROUTINE MATTERS

Refer to 1250 TEMPORARY WORKS & SERVICES for protection requirements.
Refer to 1270 CONSTRUCTION for requirements relating to defective or damaged work, removal of protection and cleaning.

Use this standard generic clause and if appropriate add additional special requirements.

3.3
SUBSTRATE

Ensure substrate is plumb, level and in true alignment.  Do not start erection if the substrate will not allow work of the required standard.

Complete any remedial work found necessary before framing erection.

3.4
CO-ORDINATE SERVICES

Co-ordinate and co-operate with electrical and mechanical work to avoid conflict between suspension members and luminaires, diffusers, pipework and ducting. Confirm the provision of extra hangers and fixings.

Ensure co-operation with work in and above the ceiling, including the marking of specific major access points to above-ceiling services. Colour coded markings to follow the standards laid down by mechanical and electrical services.
Services and other attachments, attached to or supported by the ceiling grid system to AS/NZS 2785, ensure that:

  • items over 7.5kg and items under 7.5kg, but falling greater than 3m, require a tether to AS/NZS 2785, anchored to structure.
  • items attached to the ceiling grid must be under 10kg mass, items over 10kg cannot be attached to the grid and must be independently supported.
  • unless designed otherwise, the ceiling system total load of services and other attachments must not exceed 3kg/m².
  • light fittings installed to AS/NZS 2785 and NZS 4219.
  • Ceiling system clearances to structure and services etc. that are not attached to the ceiling system to NZS 4219, and/or NZS 4541 for sprinklers.

Confirm loadings with manufacturer.

Note - Although items under 10kg mass are allowed, it is recommended that 7.5kg should be considered as a maximum for attaching to the grid under ULS conditions.

Direct fixed systems may be able to vary loads slightly from the above depending on fixing centres and lining capacity, discuss with manufacturer.  Also with direct fixed systems, subject to design, small lightweight light fittings may be fixed to the lining (for recessed) or lining back support (for pendants).

3.5
SITE CONDITIONS

To AS/NZS 2785: Appendix C2, Site Conditions and time of installation; Appendix C4, Inspection.

Installation generally
3.6
STANDARDS AND TOLERANCES

Refer to the general section 1270 CONSTRUCTION for general requirements.

Amend this clause to describe specific standards and tolerances to be achieved in carrying out this part of the work.  Although such tolerances are typically included in standards (NZS, AS/NZS etc) in certain circumstances it is worth restating these in this clause.

3.7
INSTALLATION - GENERAL

Install the system to AS/NZS 2785, and Rondo Professional Design Manual and Rondo Building Services Pty Ltd requirements.

Fix, erect and fit to finish rigid, plumb, square and true to line and face.

Amend clause to suit selected lining.

3.8
INSTALLATION - SPECIFIC

Refer to SELECTIONS for Rondo Building Services Pty Ltd project specific design documentation.

3.9
SETTING OUT

Set out the framing work true to line and square before starting erection.

3.10
ISOLATE

Isolate dissimilar metals with neoprene sheeting, or tape.

3.11
ACCESSIBILITY

Provide access hatches where required to the ceiling system to enable servicing, maintenance, and removal of any part can be carried out without damage to the ceiling system or lining.

As full access in all areas is clearly impractical, any special requirements for clear access will need to be defined; either by description here, or on the drawings.

3.12
PENETRATIONS

To AS/NZS 2785 and NZS 4219 generally, with sprinkler systems to NZS 4219 and/or NZS 4541.
Accommodate recessed light fittings, and services that are fixed to or pass through the ceiling system.  Provide independent support for these as necessary.

Modify clause to suit project requirements.
Sprinkler systems penetrations to NZS 4219 and/or NZS 4541

3.13
BULKHEADS

Form bulkheads to manufacturer requirements.  Diagonally brace at regular intervals to provide lateral stability.

Confirm with Manufacturer.

3.14
PROTECT EXISTING WORK

Protect adjacent existing work from damage during the installation.

Completion
3.15
COMPLETION MATTERS

Refer to 1270 CONSTRUCTION for completion requirements and if required commissioning requirements.

Use this standard generic clause and if appropriate add additional special requirements.

4
SELECTIONS

For further details on selections go to www.rondo.co.nz

Substitutions are not permitted.

Select the options to suit the project and delete options not specified.

If substitutions are permitted modify the statement above, ensure the NO SUBSTITUTIONS clause from GENERAL is treated the same.

 

Select the options to suit the project and delete options not specified.

Design documentation
4.1
RONDO SPECIFIC DESIGN

Document:

~

Submitted:

~

Available:

~

Document:

Identify Rondo specific design documents

Submitted:

Building consent, tender (or both)

Available:

Specification Contract Appendix, or describe alternative.

4.2
PRODUCER STATEMENT - DESIGN

PS1:

~

Available:

~

A PS1 from an independent engineer can be provided for a fee, this process is facilitated by Rondo.

PS1:

Identify the producer statement - design (PS1)

Available:

Specification Contract Appendix, or describe alternative.

Performance

Use these clauses if specifying by performance.

4.3
ENVIRONMENTAL REQUIREMENT

Location

Range:

Relative Humidity

~

~ - ~°C

~ % maximum

If this clause is not used and the SITE CONDITIONS clause cannot be complied with, then allowance needs to be made for a tile that will not sag over the construction period.

4.4
FIRE GROUP NUMBER

Title

Location

Group Number

~

~

~

4.5
FIRE RATING REQUIREMENT

FRR (minimum)

Ceiling

Floor system

Location

~/~/~

~

~

~

Note here if the floor system specified elsewhere.

Performance - Wind (design by contractor)
4.6
DESIGN PARAMETERS WIND - DESIGN BY CONTRACTOR

Wind design and performance criteria to AS/NZS 1170.2 as follows:

 

Parameter

Value

Design wind speed (Vdes.Ø):

~ m/s

Terrain Category (Mz,cat):

~

Shield Factor (Ms):

~

Topographic multiplier (Mt):

~

Hill-shape multiplier (Mh):

~

Lee multiplier (Mlee):

~

Internal pressure coefficient (Cp,i):

~

Fill in project values, obtain information from the project structural engineer.  These values come are critical to allow the Contractor to design the ceiling accurately.  Usually design for wind is only required if there are opening external windows/doors or other sources of wind pressure differential (including some roof spaces).

Ensure that all other general information is available in this specification or on the drawings (for instance ceiling height etc.). Refer to AS/NZS 2785, Appendix B for further information required.

Delete the clause if it does not apply and the contractor is not expected to design.

Performance - Seismic (design by contractor)
4.7
DESIGN PARAMETERS SEISMIC - DESIGN BY CONTRACTOR

Seismic design and performance criteria to NZS 1170.5 as follows:

 

Parameter

Value

Building Importance Level:

~

Design Working Life:

~

Site Sub-soil Class:

~

Near Fault Factor N(T,D):

~

Part Classification Category (P1-P7):

~

Interstorey Drift - ULS:

~ mm

Interstorey Drift - SLS:

~ mm

Fill in project values, obtain information from the project structural engineer.  These values are critical to allow the Contractor to design the ceiling accurately.  Ensure that all other general information is available in this specification or on the drawings (for instance ceiling height etc.). Refer to AS/NZS 2785, Appendix B for further information required.

Delete the clause if it does not apply and the contractor is not expected to design.

Rondo KEY-LOCK® System - direct-Fix
4.8
RONDO KEY-LOCK® DIRECT-FIX CEILING SYSTEM

Location:

~

Type/Brand:

KEY-LOCK® Direct-Fix Ceiling System

Furring Channels (FC):

~

Perimeter Trims:

~

Fasteners direct fix:

~

Ceiling height:

~

Fire rating:

~

Options:

Furring channels (FC):

#226, #314, #301, #394, or #BG01 Direct-Fix Clip.  Modify if using metal battens rather than furring channels.

Fasteners direct fix:

To suit substrate and component selection, Contact Rondo Building Services Pty Ltd.  For fixing bracket state; type, size, material fixed to (timber, steel, concrete)

Ceiling Height:

Add height if ceiling height is not indicated on the drawings.

Fire Rating:

State if the system is to be fire-rated, and confirm the compatibility of recessed lighting, air conditioning unit and ventilation outlets to the ceiling grid.

Rondo SCREWFIX® System - direct-Fix
4.9
RONDO SCREWFIX® CONCEALED CEILING SYSTEM

Location:

~

Type/Brand:

SCREWFIX® Direct-Fix Ceiling System

Primary support "C" channel:

#F38  38mm x 12mm

Furring Channels:

#F37  37mm x 23mm

Perimeter Trims:

~

Fasteners direct fix:

~

Ceiling height:

~

Fire rating:

~

Options:

Curved radius:

Nominate for curved ceiling, Delete if not required.

Perimeter Trims:

 

Fasteners direct fix:

To suit substrate and component selection, Contact Rondo Building Services Pty Ltd.  For fixing bracket state; type, size, material fixed to (timber, steel, concrete)

Ceiling Height:

Add height if ceiling height is not indicated on the drawings.

Fire Rating:

State if the system is to be fire-rated, and confirm the compatibility of recessed lighting, air conditioning unit and ventilation outlets to the ceiling grid.

Rondo XPRESS® system - direct-fix
4.10
RONDO XPRESS® DRYWALL GRID SYSTEM

Location:

~

Type/Brand:

XPRESS® Drywall Grid System

Primary support (Main Tees):

~

Secondary support (Cross Tees, wall trims, clips):

~

Wall Trims:

~

Direct fix brackets:

~

Ceiling height:

~

Fire rating:

~

Options:

Curved radius:

Nominate for curved ceiling, Delete if not required.

Primary support (Main Tees):

Either standard gauge or heavy gauge: Tee depth is 38mm with two width options 24mm and 38mm.

The face of the Main Tee is flush with the bottom of the Cross Tee, and can either be concealed or exposed.

Secondary support

- Cross Tees:

- Wall Trims:

- Clips:

Cross Tee options have the same depth (38mm) and two widths (24mm and 38mm).

Rondo wall trims are available in various profiles and size to suit a variety of architectural details.

For Wall Trims, refer to Rondo for design details, especially method of transition to abutting ceilings.

For clips, refer to Rondo XPRESS technical brochure and Contact Rondo for technical advice.

Direct fix brackets:

To suit substrate and component selection, Contact Rondo Building Services Pty Ltd.  For fixing bracket state; type, size, material fixed to (timber, steel, concrete)

Ceiling Height:

Add height if ceiling height is not indicated on the drawings.

Fire Rating:

State if the system is to be fire-rated, and confirm the compatibility of recessed lighting, air conditioning unit and ventilation outlets to the ceiling grid.

4.11
MOVEMENT JOINT

Location:

~

Brand:

~

System:

~

Joint Type:

~

Note - Joint Type can include perimeter Joint, seismic joint, and sheet joins. Add section profiles as required.

Components
4.12
PLASTERBOARD SHEET LINING

refer to 5113 PLASTERBOARD LININGS section

Delete this clause if no part of the ceiling is plasterboard.

4.13
CEILING LINING

Location:

~

Brand / type:

~

Thickness:

~

Grade:

~

Treatment:

~

Edge treatment:

~

Fixing type:

~

Joint type:

~

Finish:

~

Options:

Ceiling lining Type - list type other than plasterboard sheet

Section - cross reference to the Masterspec Section relevant to the type of ceiling lining.

Delete this clause if using plasterboard ceilings only.

Accessories

Refer to Rondo for design assistance and advice.

4.14
ACCESS PANEL

Location:

~

Brand:

PANTHER®

Panel Type:

~

Part number:

~

Edge detail:

~

Panel Finish/colour:

~

Size:

~mm x ~mm

Fire Rating:

~

Sound Rating:

~

Hardware/Security:

~

Options:

Panel Type:

Specialised Architectural Panels; Sound Rated (RW30); Fire-Rated (1-hr and 2hr); Non-Sound Rated Metal Faced; High-Performance Access Panel (RW51).

Refer to RONDO website for PANTHER panel details.

Part number:

Refer to RONDO website for PANTHER panel details.

Edge Detail:

Feathered Edge; Flanged Edge; Set Bead.  Refer to PANTHER panel details.

Panel Finish/Colour

Varies. Refer to PANTHER panel type listed in RONDO website.

Size:

Refer to RONDO website for PANTHER panel details.

Fire Rating:

1hr or 2hr. Delete if not applicable.

Sound Rating:

RW30 is standard;

RW51 for the High Performance Access Panel (HP-51).

Delete if not applicable.

Hardware (lock type):

Budget, standard, cam-lock, touch latch, and coin lock.

Refer to product manual. Delete if not applicable.

Access Panels for wet areas:

Refer to Wet Area Access Panel series listed under Specialised Architectural Panels.

Delete if not applicable.