If you have pre-customised this work section using the "questions and answers" provided as part of the downloading process, it may be necessary to amend some clauses to suit the final project-specific version.
The section must still be checked and customised to suit the project being specified, by removing any other irrelevant details and adding project-specific details and selections.
This section relates to the supply and installation of Earthwool® glasswool thermal and acoustic insulation.
It includes:
Modify or extend the above description to suit the project being specified.
NOTE - Retrofitting exterior walls or internal firewalls, insulation requires a Building Consent to the Building Act 2004, Schedule 1, Clause 13.
Earthwool® glasswool insulation is a bio-soluble glasswool made using up to 80% recycled glass, bonded with ECOSE® Technology, a bio-based binder using rapidly renewable materials instead of petro-based chemicals. It contains no added formaldehyde, dyes or artificial colours. Earthwool® glasswool insulation has a zero Ozone Depletion Potential (ODP) rating, and Global Warming Potential (GWP) of zero.
Note that not all products listed in SELECTIONS are currently covered by BRANZ Appraisal 648 and CodeMark certificate CMNZ30095 Products not covered have been identified in SELECTIONS.
Refer to ~ for ~
Refer to 4161 UNDERLAYS, FOIL AND DPC for underlays, foil, DPC and for wire netting used to support insulation.
Refer to blown-in insulation section, for areas where installing batt insulation is impractical.
Include cross references to other sections where these contain related work.
Refer to roofing sections for roofing underlays.
Refer to the general section 1232 INTERPRETATION & DEFINITIONS for abbreviations and definitions used throughout the specification.
The following abbreviations apply specifically to this section:
IIC | Impact insulation class |
STC | Sound Transmission Class rating |
STC is the amount of airborne sound transmission loss through a complete construction like a wall or floor, measured in decibels (dB).
IIC is the amount of impact sound transmission loss through a complete construction like a floor, measured in decibels (dB).
Rw or Weighted Sound Reduction Index is sometimes used, the Rw numbers will be very similar to the equivalent STC numbers.
Refer to the general section 1233 REFERENCED DOCUMENTS. The following documents are specifically referred to in this section:
NZBC C/AS2 | Protection from Fire |
NZBC G6/VM1 | Airborne and impact sound |
Electrical installations (Known as the Australian/New Zealand Wiring Rules) | |
Fire hazard testing - Test flames - Needle-flame test method - Apparatus, conformity test arrangement and guidance | |
Energy efficiency - Installing bulk thermal insulation in residential buildings | |
CodeMark™ CMNZ30095 verC | Knauf Insulation |
Documents listed above and cited in the clauses that follow are part of this specification. However, this specification takes precedence in the event of it being at variance with the cited document.
Delete from the DOCUMENTS clause any document not cited. List any additional cited documents.
NZS 4246 refers to AS/NZS 60695.11.5 and AS/NZS 60598.2.2 (2001 & 2016). The Electricity (Safety) Regulations 2010 only refer to AS/NZS 60598.2.2:2001.
AS/NZS 3000:2007 is cited in the Electricity (Safety) Regulations 2010, which is cited by NZBC G9/VM1. AS/NZS 3000:2018 is cited in NZBC C/AS1-AS2 Appendix in relation to smoke control in air handling systems. This section uses both versions where they equally apply, and a date is suffixed where there is a difference e.g. the 2018 version covers most recent technologies. Amend the section if you want to use a particular version or a particular instance (by suffixing with the version date e.g. AS/NZS 3000:2018).
The following are related documents and if referred to in the work section need to be added to the list of DOCUMENTS.
NZBC C/AS1 | Protection from Fire |
NZBC G6/AS1 | Airborne and impact sound |
Timber-framed buildings | |
ISO 16283.1 | Airborne sound insulation |
Insulation of lightweight-framed and solid-timber houses | |
AS/NZS 60598.2.2:2001 | Luminaires- Particular Requirements - Recessed luminaires |
AS/NZS 60598.2.2:2016 | Luminaires- Particular Requirements - Recessed luminaires |
BRANZ BU 461 | Practical sound control |
BRANZ BU 539 | Recessed downlights |
Electricity (Safety) Regulations 2010
Manufacturer and supplier documents relating to this part of the work:
Earthwool® glasswool Insulation Technical Data Sheets
Earthwool® glasswool Insulation Material Safety Data Sheets
Earthwool® glasswool Insulation Installation Instructions
BRANZ Appraisal 648 (2022) - Knauf Glasswool Insulation
Manufacturer/supplier contact details
Company: | Knauf Insulation Limited |
Web: | |
Email (Technical): | tech.nz@knaufinsulation.com |
Email (Sales): | sales.nz@knaufinsulation.com |
Telephone: | 0800 KNAUFI (562 834) |
It is important to ensure that all personnel on site have access to accurate, up to date technical information on the many products, materials and equipment used on a project. In most cases individual products are not used in isolation, but form part of a building process. Also a particular manufacturer and/or supplier requirements for handling, storage, preparation, installation, finishing and protection of their product can vary from what might be considered the norm. Access to technical information can help overcome this potential problem.
Provide a warranty for:
50 years: | For unfaced Earthwool® glasswool insulation materials |
15 years: | For Earthwool® glasswool insulation underfloor |
Refer to the general section 1237 WARRANTIES for additional requirements.
Modify or expand the clause to suit project or manufacturer/supplier requirements, options include:
Provide an installer/applicator warranty:
2 years | For installation workmanship |
Refer to the general section 1237 WARRANTIES for additional requirements.
Modify or expand the clause to suit project or manufacturer/supplier requirements, options include:
Refer to 1270 CONSTRUCTION for requirements relating to experience, skill, and qualifications.
Substitutions are not permitted to any of the specified systems, components and associated products listed in this section.
Provide sound rated systems as detailed in SELECTIONS.
Use site performance testing only where this is specifically required. To meet NZBC G6/AS1, acoustic insulation density must be 10kg/m³ or greater at 75mm thickness.
Site testing of each sound rated element (wall, ceiling etc), where required, will be carried out by the element system provider, to NZBC G6/VM1, using a nominated acoustic consultant. Coordinate with element provider to rectify any element that does not meet the specified STC/IIC figure due to insulation issues.
Refer to the appropriate wall/ceiling system sections that require sound ratings.
Use site performance testing only where this is specifically required and specifically stated in the appropriate wall/ceiling system sections (ie. plasterboard lining etc.).
Exposed acoustic blanket and/or bafflestacks in ceilings spaces forming air handling plenums, to have a Group Number to NZBC C/AS2, Table 4.4.
Insulation of HVAC ducts to have a Group Number to NZBC C/AS2, Table 4.4.
Delete or modify the clause if, the project is not designed to NZBC C/AS2, or there is no insulation of air handling plenums or ducts involved.
NOTE - Insulation (excludes foamed plastics) in plenums for NZBC C/AS1 and C/AS2, does not require a group number.
Duct Group Numbers do vary with different situations. Consult with the project Fire Consultant and/or the Services Engineer if necessary.
Earthwool® glasswool insulation is deemed non-combustible in accordance with AS 1530.1 and non-combustible to test criteria under the 30's Needle Flame Test to AS/NZS 60695.11.5.
When insulation abutting or covering recessed downlights is intended to be in contact with IC, CA 80, CA 135 luminaries the insulation must withstand a 30's Needle Flame test to AS/NZS 60695.11.5. Earthwool® glasswool insulation meets this requirement.
Earthwool® glasswool insulation meets the requirements of the NZBC when used in accordance with the conditions and limitations of its Certificate of Conformity CMNZ30095.
The CodeMark certificate provides third parties compliance to NZBC Clauses and standards specified within the certificate, provided that installation of the system is in accordance with conditions and limitations of its Certificate of Conformity.
Earthwool® glasswool insulation: Wall, non-combustible and certified Red List Free glasswool insulation segments to AS/NZS 4859.1, manufactured using up to 80% recycled glass with DriTherm® silicone treatment, ECOSE® Technology plant-based binder and TwinTech® smooth finish on both faces. Suitable for acoustic applications to NZBC G6/AS1. Available in a range of segment sizes, thicknesses, acoustic value, density and R-value. Refer to SELECTIONS.
Suitable for external wall, internal wall and mid-floor applications in new and existing timber framed and steel framed buildings.
Earthwool® glasswool insulation: Ceiling, non-combustible and certified Red List Free glasswool insulation segments to AS/NZS 4859.1, manufactured using up to 80% recycled glass with DriTherm® silicone treatment, ECOSE® Technology plant-based binder and TwinTech® smooth finish on both faces. Suitable for acoustic applications to NZBC G6/AS1. Available in ceiling and skillion roof variations in a range of segment sizes, thicknesses, acoustic value, density and R-values. Refer to SELECTIONS.
Suitable for ceiling level, skillion roof and mid-floor applications in new and existing timber framed and steel framed buildings.
Knauf Insulation: Multi-use Roll, non-combustible glasswool insulation rolls to AS/NZS 4859.1, manufactured using up to 80% recycled glass with DriTherm® silicone treatment, ECOSE® Technology plant-based binder and TwinTech® smooth finish on both faces. Suitable for acoustic applications to NZBC G6/AS1. Available in rolls 90mm thick x 430mm and 580mm wide x 8.5m long with R-value of 2.6. Refer to SELECTIONS.
Suitable for ceiling level, external wall, internal wall and mid-floor applications in new and existing timber framed and steel framed buildings.
Refer to 4161 UNDERLAYS, FOIL AND DPC for wire netting used to support the insulation.
Galvanized hexagonal 50mm mesh from 1mm diameter steel wire to AS/NZS 4534.
Proprietary plastic strapping tape.
Stapled over framing to retain insulation in unlined wall, ceiling and underfloor locations.
Required for NZBC E2/AS1 9.1.8.5 Wall framing behind cavities, where stud spaces are greater than 450mm and only flexible underlay is used.
Refer to NZS 4246, 5.3.2 Installing blanket and segments, 5.4.2 Retrofitting insulation in exterior walls without wall underlay with direct fixed claddings, 5.4.3 Retrofitting insulation in exterior walls without wall underlay with drained cavity / veneer, or 6.3 Segments and blanket insulation- unlined ceilings, depending on situation.
Not recommended where insulation is exposed over exposed sprinkler heads. In this case galvanized wire or wire netting support should be used to avoid the risk of a fire event affecting the sprinkler heads performance.
Refer to 1270 CONSTRUCTION for requirements relating to delivery, storage and handling of products.
Do not use damaged or wet insulation material.
Use this standard generic clause and if appropriate add additional special requirements.
Refer to 1250 TEMPORARY WORKS & SERVICES for protection requirements.
Refer to 1270 CONSTRUCTION for requirements relating to defective or damaged work, removal of protection and cleaning.
Use this standard generic clause and if appropriate add additional special requirements.
Check work previously carried out and confirm it is of the required standard for this part of the work
Refer to the general section 1270 CONSTRUCTION for general requirements.
Amend this clause to describe specific standards and tolerances to be achieved in carrying out this part of the work. Although such tolerances are typically included in standards (NZS, AS/NZS etc) in certain circumstances it is worth restating these in this clause.
Lay, install, fit and fix insulation without gaps, tucks, folds and over compaction to NZBC H1/AS1 or AS2 and Earthwool Installation Instructions. For all housing and buildings up to 300m², install in accordance to NZS 4246 sections 5 Walls, 6 Ceilings & Roofs, 7 Underfloor - Suspended Framed Floors and 10 Concrete Slab-on-Ground Insulation, for residential light timber or steel framed buildings. Allow insulation to re-loft/relax prior to installation. Do not cover vents. Lift up electrical wires, lighting transformers/controllers and lay the insulation underneath.
These standards give minimum building element thermal resistance (R-values). Achieving these will depend on the quality of the insulation.
CAUTION: Electrical cables and equipment partially or completely surrounded with bulk thermal insulation may overheat and fail. This applies to wiring installed prior to 1989.
Non-residential recessed light fittings to AS/NZS 3000, 4.5.2.3.5;
Refer to clause INSULATION CLEARANCES GENERALLY for clearances.
Insulation abutting or covering recessed downlights must pass the needle flame test to AS/NZS 60695.11.5, as required by AS/NZS 60598.2.2: 2001 (cited in Electricity (Safety) Regulations, Schedule 4).
Note; CA 80, CA135, IC, IC-F & NON-IC are cited in AS/NZS 60598.2.2: 2001. But CA 90, CA135, IC, IC-4 and Do-not Cover, are only in AS/NZS 60598.2.2: 2016, which makes CA 90, IC-4 & Do-not Cover, alternative solutions. However all clearances stated comply with AS/NZS 60598.2.2: 2016 and AS/NZS 3000:2018.
IC-4 due to low/zero air transfer requirements, is generally recommended for unventilated roof spaces, like skillion/compact and Passive House roofs.
Residential recessed light fittings to AS/NZS 3000, 4.5.2.3.5;
Refer to clause INSULATION CLEARANCES GENERALLY for clearances.
Insulation abutting or covering recessed downlights must pass the needle flame test to AS/NZS 60695.11.5, as required by AS/NZS 60598.2.2: 2001 (cited in Electricity (Safety) Regulations, Schedule 4 and NZS 4246).
Note; CA 80, CA135, IC & IC-F are cited in AS/NZS 60598.2.2: 2001. But CA 90, CA135, IC, & IC-4, are only in AS/NZS 60598.2.2: 2016, which makes CA 90 & IC-4 fittings alternative solutions. However all insulation clearances for all the above fittings comply with NZS 4246.
IC-4 due to low/zero air transfer requirements, is generally recommended for unventilated roof spaces, like skillion/compact and Passive House roofs.
Insulation may need to have a gap to some mechanical and electrical services and equipment, including ducts and chimneys. The gaps should be to the NZS 4246 based tables below or to the equipment manufacturer requirements if they require larger gaps. Smaller gaps to manufacturer requirements can be used for equipment specifically manufactured with heat shielding or similar (excludes light fittings). Installed gap not to be more than 50mm bigger than the required gap.
The following tables are subject to
INSULATION CLEARANCES FROM RECESSED LIGHT FITTINGS
Type of fitting | Minimum insulation clearance | Comments |
Recessed, marked NON-IC, or unmarked | 100mm(increase if over 100W) | NON-IC fittings and new or old unmarked & unknown fittings, and/or insulation. Secure insulation. |
Recessed, CA 80, CA 90 or CA 135 | Abut fittings | Do NOT cover the fittings |
Recessed, IC, IC-F or IC-4 | Abut & cover fittings | Ensure insulation complies |
Recessed, marked Do-Not-Cover | Manufacturers clearances |
|
Independent control gear | Place on top of insulation and 50mm from fitting | If not on top allow 50mm clearance to insulation, do not cover. Includes, transformers, ballasts & drivers etc. Maintain clearance by placing guard around control gear, refer to NZS 4246 figure 15. |
Surface fittings not exposed to insulation | Nil | Where surface fittings are isolated from insulation by appropriate linings. Excludes high heat fittings. |
Surface fittings & exposed insulation | 200mm | This is exposed insulation to any part of the exposed fitting & bulb/tube (e.g. exposed light in an unlined basement). Secure insulation. |
Note; CA 80, CA135, IC, IC-F & NON-IC are cited in AS/NZS 60598.2.2: 2001. But CA 90, CA135, IC, IC-4 and Do-not Cover, are only in AS/NZS 60598.2.2: 2016, which makes CA 90, IC-4 & Do-not Cover fittings, alternative solutions.
However for residential applications all insulation clearances for all the above fittings comply with NZS 4246.
But for Non-residential all clearances stated comply with AS/NZS 60598.2.2: 2016 and AS/NZS 3000:2018.
FOR MINIMUM INSULATION CLEARANCES TO INBUILT RECESSED HOT APPLIANCES - REFER TO NZS 4246
INSULATION CLEARANCES FROM EXTRACTS, VENTS, PIPES & ROOF UNDERLAY
Application | Minimum insulation clearance | Comments |
Ducted fan motors | 50mm | Includes ducted rangehoods, extractors etc. Applies to the motor unit and electrical enclosures (not the ducts). |
Ducted fan ducts | Abut | Excludes motor unit and electrical enclosures. |
Unducted fan motors usually discharging to ceiling space | 200mm | Includes unducted, rangehoods, extractors etc, discharging into roof space. To prevent debris falling into motor. Clearance may be able to be reduced, by providing a fixed barrier around the vent. |
Passive vents (still in use) | 200mm | To prevent debris falling through. Clearance may be able to be reduced, with more cohesive insulation, like some of the rigid plastic types or providing a fixed barrier around the vent. |
Plumbing penetrations through floors | 100mm | Keep gap between pipe penetration and floor insulation in case of leaks. |
Roofing material/underlay | 25mm | From underside of roofing or flexible roofing underlay, to prevent wicking. |
Note; unducted fans (bathroom & kitchen extracts) and passive vents discharging into ceiling spaces are not recommended and are probably difficult to achieve under the NZBC, but may be encountered in existing buildings.
Modify this whole clause to suit the project requirements.
These tables in part, may repeat some information that is also in other clauses, usually it is not identical and provides further detail. It is an option to delete the repeated information from here or the other related clause if it is necessary, or leave both instances to reinforce the point.
Lay at right angles across the rafters/roof joists (under purlins). Pull tight and fix.
If fitting insulation under purlins, use this clause but modify to suit. Plastic strapping may also be suitable.
Metal wire/wire netting recommended for situations where exposed insulation is over exposed sprinkler heads.
Delete clause if not required.
Lay at right angles across the framing at a minimum of 300mm centres, staple tape to each framing member with stainless steel staples.
Cut insulation using a sharp craft knife.
Measure distance between studs and cut Earthwool® glasswool insulation segments/rolls minimum 10mm wider and friction fit between framing members with front face of insulation flush with framing. Leave no gaps and maintain full thickness of insulation over whole installation. If cavity depth is greater than the insulation nominal thickness, fix or strap the insulation to secure. Cut insulation pieces as required to fill small spaces, behind outlet boxes, gaps around penetrations and other obstructions. Without compressing, tuck insulation behind wiring, plumbing or ductwork.
Measure distance between studs and cut Earthwool® glasswool insulation segments/rolls minimum 10mm wider and friction fit with one side of the segment in the metal C-channel and other edge butted against the next metal stud. Leave no gaps and maintain full thickness of insulation over whole installation. If cavity depth is greater than the insulation nominal thickness, fix or strap the insulation to secure. Cut insulation pieces as required to fill small spaces, behind outlet boxes, gaps around penetrations and other obstructions. Without compressing, tuck insulation behind wiring, plumbing or ductwork.
Friction fit Earthwool® glasswool insulation segments/rolls between floor joists, leaving no gaps and maintaining full thickness of insulation over whole installation. Cut insulation pieces as required to fill small spaces, gaps around penetrations and other obstructions. Without compressing, tuck insulation behind wiring, plumbing or ductwork where possible.
Friction fit Earthwool® glasswool insulation segments/rolls between ceiling framing members, leaving no gaps and maintaining full thickness of insulation over whole installation. R7.0 & R8.0 Ceiling batts are designed to expand over truss chords / ceiling joists without the need for notching of batts. Cut insulation pieces as required to fill small spaces, gaps around penetrations and other obstructions. Without compressing, tuck insulation behind wiring, plumbing or ductwork.
Loose lay Earthwool® glasswool insulation rolls over the ceiling framing and between truss chords, leaving no gaps and maintaining full thickness of insulation over whole installation. Cut insulation pieces as required to fill small spaces, gaps around penetrations and other obstructions. Without compressing, tuck insulation behind wiring, plumbing or ductwork.
Note: 90mm high density (wall) product can be used as the first layer of a double layer system layer and is extremely effective as it is the same height as the bottom chord of the truss or joist.
Friction fit Earthwool® glasswool insulation segments/rolls between ceiling framing members, level with the top of the framing. Loose lay a layer of Earthwool® glasswool insulation rolls over the ceiling framing, laid at 90° to the framing direction. Leave no gaps and maintain full thickness of insulation over whole installation. Cut insulation pieces as required to fill small spaces, gaps around penetrations and other obstructions. Without compressing, tuck insulation behind wiring, plumbing or ductwork.
Note - 90mm high density (wall) product can be used as the first layer of a double layer system layer and is extremely effective as it is the same height as the bottom chord of the truss or joist.
Where perimeter of ceiling space is too low to allow full depth of insulation plus the 25mm air gap to the underlay, provide reduced perimeter insulation to NZS 4246. 6.2, and maintain the 25mm gap.
Install, to manufacturer requirements, in ceiling voids with sufficient compression to maintain stability above the wall below. Cut and trim to seal round ducts, piping and other services to ensure that there are no gaps or openings allowing sound to travel. Adequate ventilation is required around electrical fittings due to heat given off.
Modify to suit the project requirements. Too much compression can compress the ceiling tiles and too little will affect the expected performance.
Refer to 1270 CONSTRUCTION for completion requirements and if required commissioning requirements.
Earthwool® glasswool insulation packaging is recyclable.
Use this standard generic clause and if appropriate add additional special requirements.
For further details on selections go to www.knauf.com/en-NZ/knauf-insulation
Substitutions are not permitted to the following, unless stated otherwise.
If substitutions are permitted modify the statement above, ensure the NO SUBSTITUTIONS clause from GENERAL is treated the same.
Select the options to suit the project and delete options not specified.
Location: | ~ |
Brand: | Earthwool® glasswool insulation |
Product: | ~ |
Application: | ~ |
Framing type: | ~ |
R-Value: | R ~ |
Thickness: | ~ mm |
Size: | ~ mm x ~ mm |
Density: | ~ kg/m³ |
Note: To meet NZBC G6/AS1, acoustic insulation must be 75mm minimum thickness and 10kg/m³ minimum density. The use of insulation below 90mm thickness as a proposed alternative solution requires field testing to NZBC G6/VM1 to demonstrate compliance.
Application: Exterior wall (thermal & acoustic)
Interior wall (acoustic)
Framing type: Timber / Steel
Product: | R-value: | Thickness: | Size: | Density (kg/m3): |
Wall segments | R1.3 | 45mm | 450mm x 1160mm | 20.5 |
| R2.2 | 90mm | 580mm x 1160mm | 10.8 |
| R2.4 | 90mm | 580mm x 1160mm | 14.6 |
| R2.6 Soundshield | 90mm | 430mm x 1160mm | 20.1 |
| R2.6 Soundshield | 90mm | 580mm x 1160mm | 20.1 |
| R2.8 Soundshield Plus | 90mm | 430mm x 1160mm | 30.7 |
| R2.8 Soundshield Plus | 90mm | 580mm x 1160mm | 30.7 |
| R3.2 (not covered by BRANZ Appraisal) | 140mm | 580mm x 1160mm | 9.3 |
| R3.6 (not covered by Codemark) | 140mm | 580mm x 1160mm | 13.4 |
| R4.1 Soundshield Plus | 140mm | 580mm x 1160mm | 22.6 |
| R4.4 Soundshield Plus | 140mm | 580mm x 1160mm | 36.0 |
|
|
|
|
|
Knauf Multi-use roll | R2.6 (not covered by BRANZ Appraisal) | 90mm | 430mm x 8.5m | 20.1 |
| R2.6 (not covered byBRANZ Appraisal) | 90mm | 580mm x 8..5m | 20.1 |
Location: | ~ |
Brand: | Earthwool® glasswool insulation |
Product: | ~ |
R-Value: | R ~ |
Thickness: | ~ mm |
Size: | ~ mm x ~ mm |
Density: | ~ kg/m³ |
The full range of unfaced Earthwool® glasswool products can be used for mid-floor applications [however quilted underfloor batt may not be suitable where recessed downlights are located].
Note: To meet NZBC G6/AS1, acoustic insulation must be 75mm minimum thickness and 10kg/m³ minimum density.
Product: | R-value: | Thickness: | Size: | Density (kg/m3): |
Ceiling segments | R3.6 | 175mm | 430mm x 1160mm | 7.4 |
| R4.1 | 195mm | 430mm x 1160mm | 7.8 |
| R5.2 | 210mm | 430mm x 1160mm | 11.4 |
| R7.0 | 330mm | 460mm x 1200mm | 8.0 |
| R8.0 | 330mm | 460mm x 1200mm | 11.0 |
|
|
|
|
|
Ceiling / skillion roof segments | R3.2 | 105mm | 430mm x 1160mm | 26.5 |
| R5.0 | 165mm | 430mm x 1160mm | 29.0 |
| R6.0 | 215mm | 430mm x 1160mm | 17.5 |
| R7.4 | 265mm | 430mm x 1160mm | 18.0 |
|
|
|
|
|
Wall segments | R1.3 | 45mm | 450mm x 1160mm | 20.5 |
| R2.2 | 90mm | 580mm x 1160mm | 10.8 |
| R2.4 | 90mm | 580mm x 1160mm | 14.6 |
| R2.6 Soundshield | 90mm | 430mm x 1160mm | 20.1 |
| R2.6 Soundshield | 90mm | 580mm x 1160mm | 20.1 |
| R2.8 Soundshield Plus | 90mm | 430mm x 1160mm | 30.7 |
| R2.8 Soundshield Plus | 90mm | 580mm x 1160mm | 30.7 |
| R3.2 (not covered by BRANZ Appraisal) | 140mm | 580mm x 1160mm | 9.3 |
| R3.6 (not covered by Codemark) | 140mm | 580mm x 1160mm | 13.4 |
| R4.1 Soundshield Plus | 140mm | 580mm x 1160mm | 22.6 |
| R4.4 Soundshield Plus | 140mm | 580mm x 1160mm | 36.0 |
|
|
|
|
|
Knauf Multi-use roll | R2.6 (not covered by BRANZ Appraisal) | 90mm | 430mm x 8.5m | 20.1 |
| R2.6 (not covered by BRANZ Appraisal) | 90mm | 580mm x 8.5m | 20.1 |
Location: | ~ |
Location: | ~ |
Brand: | Earthwool® glasswool insulation |
Product: | ~ |
Application: | ~ |
R-Value: | R ~ |
Thickness: | ~ mm |
Size: | ~ mm x ~ mm |
Density (kg/m³) | ~ kg/m³ |
Applicationi: | Product: | R-value: | Thickness: | Segment/Roll size: | Density (kg/m3): |
Between ceiling framing | Ceiling segments | R3.6 | 175mm | 430mm x 1160mm | 7.4 |
|
| R4.1 | 195mm | 430mm x 1160mm | 7.8 |
|
| R5.2 | 210mm | 430mm x 1160mm | 11.4 |
|
| R7.0 | 330mm | 460mm x 1200mm | 8.0 |
|
| R8.0 | 330mm | 460mm x 1200mm | 11.0 |
|
|
|
|
|
|
Between ceiling framing | Knauf Multi-use roll | R2.6 (not covered by BRANZ Appraisal) | 90mm | 430mm x 8.5m | 20.1 |
|
| R2.6 (not covered by BRANZ Appraisal) | 90mm | 580mm x 8.5m | 20.1 |
|
|
|
|
|
|
Over ceiling framing | Knauf Multi-use roll | R2.6 (not covered by BRANZ Appraisal) | 90mm | 430mm x 8.5m | 20.1 |
|
| R2.6 (not covered by BRANZ Appraisal) | 90mm | 580mm x 8.5m | 20.1 |
Note: NZBC H1/AS1-AS2, 2.1.2 Schedule Method, for roofs with a roof space where the insulation is installed over the horizontal ceiling, the minimum construction R-values for a roof in all climatic zones may be reduced to R3.3 for a distance of up to 500mm from the outer edge of the ceiling perimeter where space restrictions do not allow full-thickness insulation to be installed.
Location: | ~ |
Brand: | Earthwool® glasswool insulation |
First layer product (between framing): | ~ |
R-value: | ~ |
Thickness: | ~mm |
Size: | ~mm x ~mm |
Density: | ~kg/m³ |
Second layer product (over framing): | ~ |
R-value: | ~ |
Thickness: | ~mm |
Size: | ~mm x ~mm |
Density: | ~kg/m³ |
First layer product (between ceiling framing): | R-value: | Thickness: | Segment/Roll size: | Density (kg/m3): |
Ceiling segments | R3.6 | 175mm | 430mm x 1160mm | 7.4 |
| R4.1 | 195mm | 430mm x 1160mm | 7.8 |
| R5.2 | 210mm | 430mm x 1160mm | 11.4 |
| R7.0 | 330mm | 460mm x 1200mm | 8.0 |
| R8.0 | 330mm | 460mm x 1200mm | 11.0 |
|
|
|
|
|
Knauf Multi-use roll | R2.6 (not covered by BRANZ Appraisal) | 90mm | 430mm x 8.5m | 20.1 |
| R2.6 (not covered by BRANZ Appraisal) | 90mm | 580mm x 8.5m | 20.1 |
Second layer product (over ceiling framing): | R-value: | Thickness: | Segment/Roll size: | Density (kg/m3): |
Knauf Multi-use roll | R2.6 (not covered by BRANZ Appraisal) | 90mm | 430mm x 8.5m | 20.1 |
| R2.6 (not covered by BRANZ Appraisal) | 90mm | 580mm x 8.5m | 20.1 |
Note: NZBC H1/AS1-AS2, 2.1.2 Schedule Method, for roofs with a roof space where the insulation is installed over the horizontal ceiling, the minimum construction R-values for a roof in all climatic zones may be reduced to R3.3 for a distance of up to 500mm from the outer edge of the ceiling perimeter where space restrictions do not allow full-thickness insulation to be installed.
Location: | ~ |
Brand: | Earthwool® glasswool insulation |
Density (kg/m³) | ~ kg/m³ |
R-Value: | R ~ |
Thickness: | ~ mm |
Size: | ~ mm x ~ mm |
Select accordingly to suit performance requirement.
Density (kg/m³) | R-value: | Thickness: | Size: |
14.0 | R2.0 | 75 mm | 580 mm x 1160 mm |
20.0 | R2.6 | 90 mm | 430 mm x 1160 mm |