4721EW
EARTHWOOL® GLASSWOOL ACOUSTIC INSULATION
1
GENERAL

If you have pre-customised this work section using the "questions and answers" provided as part of the downloading process, it may be necessary to amend some clauses to suit the final project-specific version.

 

The section must still be checked and customised to suit the project being specified, by removing any other irrelevant details and adding project-specific details and selections.

 

This section relates to Earthwool® glasswool thermal and acoustic insulation systems including installation.

It includes:

Earthwool® glasswool insulation

Modify or extend the above description to suit the project being specified.

 

NOTE - Retrofitting exterior walls or internal firewalls, insulation requires a Building Consent to the Building Act 2004, Schedule 1, Clause 13.

1.1
RELATED WORK

Refer to ~ for ~

Refer to 4161 UNDERLAYS, FOIL AND DPC for wall underlay and roofing underlay..

Refer to 4721JS JET STREAM® MAX blown-in insulation, for areas where installing batt insulation is impractical.

Include cross references to other sections where these contain related work.

Refer to roofing sections for roofing underlays.

1.2
ABBREVIATIONS AND DEFINITIONS

Refer to the general section 1232 INTERPRETATION & DEFINITIONS for abbreviations and definitions used throughout the specification.

 

The following abbreviations apply specifically to this section:

IIC

Impact insulation class

STC

Sound Transmission Class rating

STC is the amount of airborne sound transmission loss through a complete construction like a wall or floor, measured in decibels (dB).

IIC is the amount of impact sound transmission loss through a complete construction like a floor, measured in decibels (dB).

Rw or Weighted Sound Reduction Index is sometimes used, the Rw numbers will be very similar to the equivalent STC numbers.

Documents
1.3
DOCUMENTS

Refer to the general section 1233 REFERENCED DOCUMENTS.  The following documents are specifically referred to in this section:

NZBC C/AS1-AS2

Protection from Fire

NZBC G6/AS1

Airborne and impact sound

NZBC G6/VM1

Airborne and impact sound

AS/NZS 3000

Electrical installations (Known as the Australian/New Zealand Wiring Rules)

AS/NZS 5110

Recessed Luminaire Barriers

AS/NZS 60695.11.5

Fire hazard testing - Test flames - Needle-flame test method - Apparatus, conformity test arrangement and guidance

NZS 4246

Energy efficiency - Installing bulk thermal insulation in residential buildings

 

Documents listed above and cited in the clauses that follow are part of this specification.  However, this specification takes precedence in the event of it being at variance with the cited document.

Delete from the DOCUMENTS clause any document not cited.  List any additional cited documents.

 

NZS 4246 refers to AS/NZS 60695.11.5 and AS/NZS 60598.2.2 (2001 & 2016). The Electricity (Safety) Regulations 2010 only refer to AS/NZS 60598.2.2:2001.

 

AS/NZS 3000:2007 is cited in the Electricity (Safety) Regulations 2010, which is cited by NZBC.  At the time of writing, however, AS/NZS 3000:2018 is not cited.   This section uses both versions where they equally apply, and a date is suffixed where there is a difference e.g. the 2018 version covers most recent technologies.  Amend the section if you want to use a particular version or a particular instance (by suffixing with the version date e.g. AS/NZS 3000:2018).

 

The following are related documents and if referred to in the work section need to be added to the list of DOCUMENTS.

NZS 3604

Timber-framed buildings

ISO 16283.1

Airborne sound insulation

SNZ/PAS 4244

Insulation of lightweight-framed and solid-timber houses

AS/NZS 60598.2.2:2001

Luminaires- Particular Requirements - Recessed luminaires

AS/NZS 60598.2.2:2016

Luminaires- Particular Requirements - Recessed luminaires

BRANZ BU 461

Practical sound control

BRANZ BU 539

Recessed downlights

Electricity (Safety) Regulations 2010

1.4
MANUFACTURER/SUPPLIER DOCUMENTS

Manufacturer and supplier documents relating to this part of the work:

 

BRANZ Appraisal 648

Earthwool® glasswool Insulation

CodeMark

GM-CM30095-RevA1

 

Refer to conditions and limitations listed in the CodeMark.

 

Refer to Compliance clause CODEMARK CERTIFICATE for list of

 

Product Datasheets and Installation Guidelines

GreenTag

KNI-001-v2-2016

 

Manufacturer/supplier contact details

Company:

Knauf Insulation New Zealand

Web:

www.knaufinsulation.co.nz

Email (Technical):

tech.nz@knaufinsulation.com

Email (Sales):

sales.nz@knaufinsulation.com

Telephone:

0800 KNAUFI (562 834)

It is important to ensure that all personnel on site have access to accurate, up to date technical information on the many products, materials and equipment used on a project.  In most cases individual products are not used in isolation, but form part of a building process.  Also a particular manufacturer and/or supplier requirements for handling, storage, preparation, installation, finishing and protection of their product can vary from what might be considered the norm.  Access to technical information can help overcome this potential problem.

Warranties
1.5
WARRANTY

Provide a warranty for:

50-years:

For unfaced Earthwool® glasswool insulation materials

15-years:

For Earthwool® glasswool insulation underfloor

 

  • Provide this warranty on the manufacturer/supplier standard form (if not available then use the standard form in the general section 1237WA WARRANTY AGREEMENT)
  • Commence the warranty from the date of practical completion of the contract works.

 

Refer to the general section 1237 WARRANTIES for additional requirements.

~ years to ~ years are the sort of warranty periods that can be expected depending on material selection and project conditions.  Check with the manufacturer/supplier for their specific periods.

 

Modify or expand the clause to suit project or manufacturer/supplier requirements, options include:

  • Modify the form to be used
  • Commence the warranty from the date of purchase (check with the manufacturer/supplier)
1.6
WARRANTY INSTALLER / APPLICATOR

Provide an installer/applicator warranty:

~ - years

For installation of insulation

 

  • Provide this warranty on the installer/applicator standard form (if not available then use the standard form in the general section 1237WA WARRANTY AGREEMENT).
  • Commence the warranty from the date of practical completion of the contract works.

 

Refer to the general section 1237 WARRANTIES for additional requirements.

~ years to ~ years are the sort of warranty periods that can be expected depending on material selection and project conditions.  Check with the manufacturer/supplier for their specific periods.

 

Modify or expand the clause to suit project or manufacturer/supplier requirements, options include:

  • Modify the form to be used
  • Commence the warranty from the date of purchase (check with the manufacturer/supplier)
Requirements
1.7
QUALIFICATIONS - GENERAL

Refer to 1270 CONSTRUCTION for requirements relating to experience, skill, and qualifications.

1.8
NO SUBSTITUTIONS

Substitutions are not permitted to any of the specified systems, components and associated products listed in this section.

Performance - acoustic insulation
1.9
SOUND RATING REQUIREMENTS

Provide sound rated systems as detailed in SELECTIONS.

Use site performance testing only where this is specifically required.  To meet NZBC G6/AS1, acoustic insulation density must be 10kg/m³ or greater at 75mm thickness.

1.10
SOUND CONTROL SITE TEST

Site testing of each sound rated element (wall, ceiling etc), where required, will be carried out by the element system provider, to NZBC G6/VM1, using a nominated acoustic consultant.  Coordinate with element provider to rectify any element that does not meet the specified STC/IIC figure due to insulation issues.

Refer to the appropriate wall/ceiling system sections that require sound ratings.

Use site performance testing only where this is specifically required and specifically stated in the appropriate wall/ceiling system sections (ie. plasterboard lining etc.).

1.11
SURFACE FIRE PROPERTIES

Exposed acoustic blanket and/or bafflestacks in ceilings spaces forming air handling plenums, to have a Group Number 3 or better, but only for NZBC C/AS2, Table 4.4.

Insulation of HVAC ducts to have a Group Number to NZBC C/AS2, Table 4.4.

Delete or modify the clause if, the project is not designed to NZBC C/AS2, or there is no insulation of air handling plenums or ducts involved.

NOTE - Insulation (excludes foamed plastics) in plenums for NZBC C/AS1 and C/AS2, does not require a group number.

Duct Group Numbers do vary with different situations.  Consult with the project Fire Consultant and/or the Services Engineer if necessary.

1.12
REVERBERATION CONTROL PANEL

Refer to SELECTIONS for option.

Modify to suit the system specified.  Use for acoustically absorbent systems for lining walls and ceilings; options are proprietary ceiling tile, exposed foam or fabric covered panels.  Generally used as surface mounted treatment on walls and ceilings due to excellent absorption properties.

Performance - Fire properties
1.13
FIRE PROPERTIES:

Earthwool® glasswool insulation is non-combustible to test criteria under the 30's Needle Flame Test to AS/NZS 60695.11.5.

When insulation abutting or covering recessed downlights is intended to be in contact with IC, CA 80, CA 135 luminaries the insulation must withstand a 30's Needle Flame test to AS/NZS 60695.11.5.  Earthwool® glasswool insulation meets this requirement.

Compliance

NZBC H1 describes three methods to show compliance with the insulation requirements in H1: Schedule Method, Calculation Method, and Building Performance Index (BPI).

1.14
CODEMARK CERTIFICATE

Earthwool® glasswool insulation meets the requirements of the NZBC when used in accordance with the conditions and limitations of its Certificate of Conformity. Refer to MANUFACTURER/SUPPLIER DOCUMENTS for CodeMark certificate.

 

The following Earthwool® glasswool Product Datasheets and Installation Instructions are listed in the CodeMark conditions and limitations:

- Acoustic:

Product datasheet ref: KINZ0914116DS, January 2017

- Wall:

Product datasheet ref: KINZ00914114DS, January 2017

- Multi-Use roll:

Product datasheet ref: KINZ0616396DS, June 2017

- Wall Batts:

Installation instructions, ref: KINZ1017633MIS

The CodeMark certificate provides third parties compliance to NZBC Clauses and standards specified within the certificate, provided that installation of the system is in accordance with conditions and limitations of its Certificate of Conformity - Product Datasheets and Installation Instructions listed in this clause are from the CodeMark conditions and limitations.

2
PRODUCTS

Earthwool® glasswool insulation is a bio-soluble glasswool made using up to 80% recycled glass, bonded with ECOSE® Technology, a bio-based binder that uses rapidly renewable materials instead of petro-based chemicals.  It contains no added formaldehyde, dyes or artificial colours.

Earthwool® glasswool insulation has a zero Ozone Depletion Potential (ODP) rating, and Global Warming Potential (GWP) of zero.

Materials - Wall Acoustic Insulation
2.1
EARTHWOOL® GLASSWOOL: ACOUSTIC WALL BATTS

A rectangular batt to NZBC G6/AS1.  Made using recycled glass and with ECOSE® Technology, it is suitable for acoustic applications.

Refer to SELECTIONS for location, type, R-value, acoustic value, density, and thickness.

Materials - Mid-Floor Acoustic Insulation
2.2
EARTHWOOL® GLASSWOOL: ACOUSTIC BATTS

A rectangular batt to NZBC G6/AS1.  Made using recycled glass and with ECOSE® Technology, it is suitable for acoustic applications.

Refer to SELECTIONS for location, type, R-value, acoustic value, density, and thickness.

2.3
EARTHWOOL® GLASSWOOL: ACOUSTIC ROLLS

A roll of insulation to NZBC G6/AS1.  Made using recycled glass and with ECOSE® Technology, it is suitable for acoustic applications.

Refer to SELECTIONS for location, type, R-value, acoustic value, density, and thickness.

The full range of Earthwool® glasswool insulation products are available for mid-floor applications.

NOTE: When insulation abutting or covering recessed downlights is intended to be in contact with IC, CA 80, CA 135 luminaries the insulation must withstand a 30s Needle Flame test to AS/NZS 60695.11.5.  Earthwool® glasswool meets this requirement.

Materials - Ceilings Acoustic Insulation
2.4
EARTHWOOL® GLASSWOOL: ACOUSTIC BATTS

A rectangular batt to NZBC G6/AS1.  Made using recycled glass and with ECOSE® Technology, it is suitable for acoustic applications.

Refer to SELECTIONS for location, type, R-value, acoustic value, density, and thickness.

2.5
EARTHWOOL® GLASSWOOL: ACOUSTIC ROLLS

A roll of insulation to NZBC G6/AS1.  Made using recycled glass and with ECOSE® Technology, it is suitable for acoustic applications.

Refer to SELECTIONS for location, type, R-value, acoustic value, density, and thickness.

NOTE: When insulation abutting or covering recessed light fittings is intended to be in contact with IC, CA 80, CA 135 luminaries the insulation must withstand a 30s Needle Flame test to AS/NZS 60695.11.5.  Earthwool® glasswool meets this requirement.

Components
2.6
TAPES:

Polypropylene or similar strapping stapled across framing to retain insulation in wall and ceiling applications.

Accessories - General
2.7
WIRE NETTING

Refer to 4161 - WIRE NETTING, for wire netting used to support the insulation.

Wire netting is used to support roofing underlays, particularly those that are not self supporting.

Wire netting must be used to support all types of underlay where the roof has a pitch below 8°.

2.8
STUD STRAPS

Refer to Section 4161 - STUD STRAPS, where plastic straps are required for cavity construction with framing greater than 450mm centres.

2.9
VAPOUR BARRIER

 Refer to 4161 - MOISTURE VAPOUR BARRIER

3
EXECUTION
Conditions
3.1
DELIVERY, STORAGE & HANDLING OF PRODUCTS

Refer to 1270 CONSTRUCTION for requirements relating to delivery. Storage and handling of products.

Use this standard generic clause and if appropriate add additional special requirements.

Do not use damaged or wet insulation material.

3.2
ROUTINE MATTERS

Refer to 1250 TEMPORARY WORKS & SERVICES for protection requirements.

Refer to 1270 CONSTRUCTION for requirements relating to defective or damaged work, removal of protection and cleaning.

  • The building envelope must be maintained to a weathertight condition to ensure the insulation remains dry.  Cavities must be clean and dry before fitting insulation.

Use this standard generic clause and if appropriate add additional special requirements.

3.3
PRE-INSTALLATION REQUIREMENTS

Check work previously carried out and confirm it is of the required standard for this part of the work.

Location and framing

free from moisture, and that the cavities are not interconnected.

Moisture content:

~% maximum for framing

Insulation re-loft

Allow to re-loft/relax to specified thickness.

Discard

Damaged or wet insulation

Underlays

Ensure roof and wall underlays are installed, dry, clean, undamaged and free of debris before being covered with insulation

Vapour Barriers

Ensure vapour barrier forms one homogeneous sheet

Installation
3.4
INSTALLATION - GENERAL

Lay, install, fit and fix to NZBC G6/AS1 and NZBC G6/VM1 and to manufacturer requirements.  Do not cover vents.  Allow a clear gap around metal flues as recommended by the fireplace manufacturer.  Refer to manufacturer installation instructions and NZS 4246 for further details.

These standards give minimum building element thermal resistance (R-values). Achieving these will depend on the quality of the insulation.

CAUTION: Electrical cables and equipment partially or completely surrounded with bulk thermal insulation may overheat and fail. This applies to wiring installed prior to 1989.

3.5
RECESSED LIGHT FITTINGS - NON-RESIDENTIAL

Non-residential recessed light fittings to AS/NZS 3000, 4.5.2.3.5;

  • Existing fittings or retrofit situations, fittings maybe unmarked
  • New fittings can only be labelled - CA 80, CA 90, CA 135, IC, IC-F, IC-4, NON-IC or Do-not Cover

 

Refer to clause INSULATION CLEARANCES GENERALLY for clearances.

Insulation abutting or covering recessed downlights must pass the needle flame test to AS/NZS 60695.11.5, as required by AS/NZS 60598.2.2: 2001 (cited in Electricity (Safety) Regulations, Schedule 4).

 

Note; CA 80, CA135, IC, IC-F & NON-IC are cited in AS/NZS 60598.2.2: 2001.  But CA 90, CA135, IC, IC-4 and Do-not Cover, are only in AS/NZS 60598.2.2: 2016, which makes CA 90, IC-4 & Do-not Cover, alternative solutions.  However all clearances stated comply with AS/NZS 60598.2.2: 2016 and AS/NZS 3000:2018.

 

IC-4 due to low/zero air transfer requirements, is generally recommended for unventilated roof spaces, like skillion/compact and Passive House roofs.

3.6
RECESSED LIGHT FITTING CLEARANCES - RESIDENTIAL

Residential recessed light fittings to AS/NZS 3000, 4.5.2.3.5;

  • Existing fittings or retrofit situations, fittings maybe unmarked
  • New fittings can only be labelled - CA 80, CA 90, CA 135, IC, IC-F & IC-4

 

Refer to clause INSULATION CLEARANCES GENERALLY for clearances.

Insulation abutting or covering recessed downlights must pass the needle flame test to AS/NZS 60695.11.5, as required by AS/NZS 60598.2.2: 2001 (cited in Electricity (Safety) Regulations, Schedule 4 and NZS 4246).

 

Note; CA 80, CA135, IC & IC-F are cited in AS/NZS 60598.2.2: 2001.  But CA 90, CA135, IC, & IC-4, are only in AS/NZS 60598.2.2: 2016, which makes CA 90 & IC-4 fittings alternative solutions.  However all insulation clearances for all the above fittings comply with NZS 4246.

 

IC-4 due to low/zero air transfer requirements, is generally recommended for unventilated roof spaces, like skillion/compact and Passive House roofs.

3.7
INSULATION CLEARANCES - GENERAL

Insulation may need to have a gap to some mechanical and electrical services and equipment, including ducts and chimneys.  The gaps should be to the NZS 4246 based tables below or to the equipment manufacturer requirements if they require larger gaps.  Smaller gaps to manufacturer requirements can be used for equipment specifically manufactured with heat shielding or similar (excludes light fittings).  Installed gap not to be more than 50mm bigger than the required gap.

The following tables are subject to

  • The requirements of NZS 4246.
  • The insulation is exposed to the source of heat or equipment etc.
  • Insulation, has passed the needle flame test to AS/NZS 60695.11.5 and/or is non-combustible.
  • Gaps to hot surfaces may have to be increased with non-compliant insulation and plastic/polymeric type insulation (EPS, XPS, PIR, etc), check with insulation manufacturer.
  • Gaps to hot surfaces may be able to be reduced with non-combustible insulation, check with equipment manufacturer.
  • "Secure insulation" if required means, glue, mechanical fix, or provide fixed barriers at gap edge of insulation to hold in place.  Rigid or semi rigid insulation may only need a firm friction fit (secure loose pieces).

 

INSULATION CLEARANCES FROM RECESSED LIGHT FITTINGS

Type of fitting

Minimum insulation clearance

Comments

Recessed, marked NON-IC, or unmarked

100mm(increase if over 100W)

NON-IC fittings and new or old unmarked & unknown fittings, and/or insulation. Secure insulation.

Recessed, CA 80, CA 90 or CA 135

Abut fittings

Do NOT cover the fittings

Recessed, IC, IC-F or IC-4

Abut & cover fittings

Ensure insulation complies

Recessed, marked Do-Not-Cover

Manufacturers clearances

 

Independent control gear

Place on top of insulation and 50mm from fitting

If not on top allow 50mm clearance to insulation, do not cover. Includes, transformers, ballasts & drivers etc.

Maintain clearance by placing guard around control gear, refer to NZS 4246 figure 15.

Surface fittings not exposed to insulation

Nil

Where surface fittings are isolated from insulation by appropriate linings. Excludes high heat fittings.

Surface fittings & exposed insulation

200mm

This is exposed insulation to any part of the exposed fitting & bulb/tube (e.g. exposed light in an unlined basement). Secure insulation.

Note; CA 80, CA135, IC, IC-F & NON-IC are cited in AS/NZS 60598.2.2: 2001.  But CA 90, CA135, IC, IC-4 and Do-not Cover, are only in AS/NZS 60598.2.2: 2016, which makes CA 90, IC-4 & Do-not Cover fittings, alternative solutions.

However for residential applications all insulation clearances for all the above fittings comply with NZS 4246.

But for Non-residential all clearances stated comply with AS/NZS 60598.2.2: 2016 and AS/NZS 3000:2018.

FOR MINIMUM INSULATION CLEARANCES TO INBUILT RECESSED HOT APPLIANCES - REFER TO NZS 4246

 

INSULATION CLEARANCES FROM EXTRACTS, VENTS, PIPES & ROOF UNDERLAY

Application

Minimum insulation clearance

Comments

Ducted fan motors

50mm

Includes ducted rangehoods, extractors etc. Applies to the motor unit and electrical enclosures (not the ducts).

Ducted fan ducts

Abut

Excludes motor unit and electrical enclosures.

Unducted fan motors usually discharging to ceiling space

200mm

Includes unducted, rangehoods, extractors etc, discharging into roof space.

To prevent debris falling into motor.

Clearance may be able to be reduced, by providing a fixed barrier around the vent.

Passive vents (still in use)

200mm

To prevent debris falling through. Clearance may be able to be reduced, with more cohesive insulation, like some of the rigid plastic types or providing a fixed barrier around the vent.

Plumbing penetrations through floors

100mm

Keep gap between pipe penetration and floor insulation in case of leaks.

Roofing material/underlay

25mm

From underside of roofing or flexible roofing underlay, to prevent wicking.

Note; unducted fans (bathroom & kitchen extracts) and passive vents discharging into ceiling spaces are not recommended and are probably difficult to achieve under the NZBC, but may be encountered in existing buildings.

Modify this whole clause to suit the project requirements.

These tables in part, may repeat some information that is also in other clauses, usually it is not identical and provides further detail.  It is an option to delete the repeated information from here or the other related clause if it is necessary, or leave both instances to reinforce the point.

Installation - Wall Framing
3.8
TIMBER FRAMING

Friction fit between framing members and linings.  Cut on site to fill cavity and provide a close even fit.  When cutting to fill a void, oversize by up to 10mm to ensure a tight fit.  Ensure there is a friction fit on all faces of the insulation.  If cavity depth is greater than the insulation nominal thickness, fix or strap the product to secure in accordance with installation instructions.  Cut into smaller pieces for smaller spaces and around penetrations to achieve efficient thermal performance.  Do not fold, tuck or compress the insulation.  Refer to NZS 4246 for installation guidelines and Earthwool® glasswool insulation Product Data Sheets, for detailed installation instructions.

3.9
STEEL FRAMING

Friction fit inside the steel framing and cut on site to fit nog spacing.  Fill cavity and provide a close even fit.  When cutting to fill a void, oversize by up to 10mm to ensure a tight fit.  Do not fold, tuck or compress the insulation.  Cut to smaller pieces for smaller spaces and around penetrations to achieve efficient thermal performance.

Installation - Mid-floors
3.10
MID-FLOOR FRAMING

Friction fit insulation between framing members and linings.  Cut on site to fill cavity and provide a close even fit.  When cutting to fill a void, oversize by up to 10mm to ensure a tight fit.Ensure there is a friction fit on all faces of the insulation.  If cavity depth is greater than the insulation nominal thickness, fix or strap the product to ensure the insulation is installed hard against the flooring or the ceiling lining. Cut into smaller pieces for smaller spaces and around penetrations to achieve efficient thermal performance.  Refer to NZS 4246 for installation guidelines.

Installation - Ceilings
3.11
CEILING - SINGLE LAYER (BATTS BETWEEN CEILING FRAMING)

Friction fit insulation between framing members.  Cut across the roll to fit nogs and small spaces around penetrations.  Leave no gaps and maintain full thickness of insulation over the whole of the installation.  Leave gap around metal flues to the manufacturer requirements.

3.12
CEILING - SINGLE LAYER (ROLLS OVER CEILING FRAMING)

Loose lay over ceiling framing and between truss chords.  Fit securely around all penetrations, leave clearances where required.  Cut ceiling roll as required.

Note: 90mm high density (wall) product can be used as the first layer of a double layer system layer and is extremely effective as it is the same height as the bottom chord of the truss or joist.

3.13
CEILING - DOUBLE LAYER (BATTS BETWEEN FRAMING WITH ROLLS ON TOP)

Friction fit first layer of ceiling insulation roll parallel to and between ceiling framing members.  Run a second layer of insulation roll at 90° to and over the first layer over framing members. Use a sharp craft knife to cut to required size to fit nogs and small spaces around penetrations.  Leave no gaps and maintain full thickness of the insulation over the whole of the installation.  Leave gap around metal flues to manufacturer requirements.

Note - 90mm high density (wall) product can be used as the first layer of a double layer system layer and is extremely effective as it is the same height as the bottom chord of the truss or joist.

3.14
CEILING INSULATION EDGE DETAIL

Where perimeter of ceiling space is too low to allow full depth of insulation plus the 25mm air gap to the underlay, provide reduced perimeter insulation to NZS 4246. 6.2, and maintain the 25mm gap.

3.15
INSTALL BAFFLE STACK

Install, to manufacturer requirements, in ceiling voids with sufficient compression to maintain stability above the wall below.  Cut and trim to seal round ducts, piping and other services to ensure that there are no gaps or openings allowing sound to travel.  Adequate ventilation is required around electrical fittings due to heat given off.

Modify to suit the project requirements.  Too much compression can compress the ceiling tiles and too little will affect the expected performance.

3.16
LAY WIRE NETTING - UNDER JOISTS / PURLINS

Lay at right angles across the rafters/roof joists (under purlins).  Pull tight and fix.

Refer to 4161 UNDERLAYS, FOIL AND DPC for wire netting used to support the insulation.

If fitting insulation under purlins, use this clause but modify to suit.  Plastic strapping may also be suitable.

Metal wire/wire netting recommended for situations where exposed insulation is over exposed sprinkler heads.

Delete clause if not required.

3.17
INSTALL STUD STRAPS

Refer to Section 4161 - STUD STRAPS

Required for NZBC E2/AS1 9.1.8.5 Wall framing behind cavities, where stud spaces are greater than 450mm and only flexible underlay is used.

Not recommended where insulation is exposed over exposed sprinkler heads.  In this case galvanized wire or wire netting support should be used to avoid the risk of a fire event affecting the sprinkler heads performance.

Modify the clause to suit project requirements, and if using alternative to strapping e.g. wire, mesh or battens.

3.18
FIX VAPOUR BARRIER

Refer to 4161 UNDERLAYS, FOIL AND DPC for vapour barrier.

Completion & Commissioning
3.19
COMPLETION MATTERS

Refer to 1270 CONSTRUCTION for completion requirements and if required commissioning requirements.

Earthwool® glasswool insulation packaging is recyclable.

Use this standard generic clause and if appropriate add additional special requirements.

4
SELECTIONS

For further details on selections go to www.knaufinsulation.co.nz

Substitutions are not permitted to the following, unless stated otherwise.

If substitutions are permitted modify the statement above, ensure the NO SUBSTITUTIONS clause from GENERAL is treated the same.

Select the options to suit the project and delete options not specified.

Walls - Acoustic Insulation
4.1
EARTHWOOL® GLASSWOOL INSULATION: ACOUSTIC WALL BATTS (TIMBER FRAMING)

Location:

~

Brand:

Earthwool® glasswool insulation

Density (kg/m³)

~ kg/m³

R-Value:

R ~

Thickness:

~ mm

Size:

~ mm x ~ mm

Refer to the clause CODEMARK CERTIFICATE for a list of product datasheets, and performance tabled data.

Acoustic batts for internal and external timber framed walls:

Density (kg/m³)

R-value:

Thickness:

Size:

11.0

R1.3

50 mm

600 mm x 2700 mm

11.0

R1.9

75 mm

600 mm x 2700 mm

14.0

R1.4

50 mm

580 mm x 1160 mm

14.0

R2.0

75 mm

580 mm x 1160 mm

20.0

R2.6

90 mm

430 mm x 1160 mm

20.0

R2.6

90 mm

580 mm x 1160 mm

27.0

R2.8

90 mm

430 mm x 1160 mm

27.0

R2.8

90 mm

580 mm x 1160 mm

4.2
EARTHWOOL® GLASSWOOL INSULATION: ACOUSTIC WALL BATTS (STEEL FRAMING)

Location:

~

Brand:

Earthwool® glasswool insulation

Density (kg/m³)

~ kg/m³

R-Value:

R ~

Thickness:

~ mm

Size:

~ mm x ~ mm

 

Acoustic batts for internal and external steel framed walls:

Density (kg/m³)

R-value

Thickness

Size

11.0

R1.3

50 mm

600 mm x 2700 mm

11.0

R1.9

75 mm

600 mm x 2700 mm

Mid-Floor - Acoustic Insulation
4.3
EARTHWOOL® GLASSWOOL INSULATION: ACOUSTIC BATTS - MID-FLOOR

Location:

~

Brand:

Earthwool® glasswool insulation

Density (kg/m³)

~ kg/m³

R-Value:

R ~

Thickness:

~ mm

Size:

~ mm x ~ mm

NOTE:  As an alternative to Earthwool acoustic batts [listed below] the full range of Earthwool® glasswool products are available for mid-floor applications [however quilted underfloor batt may not be suitable where recessed downlights are located].

Refer to the clause CODEMARK CERTIFICATE for a list of product datasheets, and tabled data.

Acoustic Batts:

Density (kg/m³)

R-value

Thickness

Size

11.0

R1.3

50 mm

600 mm x 2700 mm

11.0

R1.9

75 mm

600 mm x 2700 mm

14.0

R1.4

50 mm

580 mm x 1160 mm

14.0

R2.0

75 mm

580 mm x 1160 mm

20.0

R2.6

90 mm

430 mm x 1160 mm

20.0

R2.6

90 mm

580 mm x 1160 mm

27.0

R2.8

90 mm

430 mm x 1160 mm

27.0

R2.8

90 mm

580 mm x 1160 mm

4.4
EARTHWOOL® GLASSWOOL INSULATION: ACOUSTIC ROLLS - MID-FLOOR

Location:

~

Brand:

Earthwool® glasswool insulation

Density (kg/m³)

~ kg/m³

R-Value:

R ~

Thickness:

~ mm

Size:

~ mm x ~ mm

NOTE:  As an alternative to Earthwool acoustic batts [listed below] the full range of Earthwool® glasswool products are available for mid-floor applications [however quilted underfloor batt may not be suitable where recessed downlights are located].

Refer to the clause CODEMARK CERTIFICATE for a list of product datasheets, and tabled data.

Acoustic Rolls:

Density (kg/m³)

R-value

Thickness

Size

12.1

R1.8

70 mm

1200 mm x 13500 mm

12.2

R2.9

115 mm

1200 mm x 8500 mm

11.0

R3.2

135 mm

1200 mm x 8000 mm

11.0

R3.6

150 mm

1200 mm x 7000 mm

Ceilings - Acoustic Insulation
4.5
EARTHWOOL® GLASSWOOL INSULATION: ACOUSTIC BATTS - CEILINGS

Location:

~

Brand:

Earthwool® glasswool insulation

Density (kg/m³)

~ kg/m³

R-Value:

R ~

Thickness:

~ mm

Size:

~ mm x ~ mm

Refer to the clause CODEMARK CERTIFICATE for a list of product datasheets, and tabled data.

 

Acoustic Batts for suspended ceilings:

Density (kg/m³)

R-value

Thickness

Size

11.0

R1.3

50 mm

600 mm x 2700 mm

11.0

R1.9

75 mm

600 mm x 2700 mm

 

Acoustic Batts for ceilings:

Density (kg/m³)

R-value

Thickness

Size

11.0

R1.3

50 mm

600 mm x 2700 mm

11.0

R1.9

75 mm

600 mm x 2700 mm

14.0

R1.4

50 mm

580 mm x 1160 mm

14.0

R2.0

75 mm

580 mm  x 1160 mm

14.0

R2.0

75 mm

430 mm x 1160 mm

20.0

R2.6

90 mm

430 mm x 1160 mm

20.0

R2.6

90 mm

580 mm x 1160 mm

27.0

R2.8

90 mm

430 mm x 1160 mm

27.0

R2.8

90 mm

580 mm x 1160 mm

4.6
EARTHWOOL® GLASSWOOL INSULATION: ACOUSTIC ROLLS - CEILINGS

Location:

~

Brand:

Earthwool® glasswool insulation

Density (kg/m³)

~ kg/m³

R-Value:

R ~

Thickness:

~ mm

Size:

~ mm x ~ mm

Acoustic Rolls for ceilings:

Density (kg/m³)

R-value

Thickness

Size

12.1

R1.8

70 mm

1200 mm x 13500 mm

12.2

R2.9

115 mm

1200 mm x 8500 mm

11.0

R3.2

135 mm

1200 mm x 8000 mm

11.0

R3.6

150 mm

1200 mm  x 7000 mm

4.7
EARTHWOOL® GLASSWOOL INSULATION: BAFFLE STACK

Location:

~

Brand:

Earthwool® glasswool insulation

Density (kg/m³)

~ kg/m³

R-Value:

R ~

Thickness:

~ mm

Size:

~ mm x ~ mm

Select accordingly to suit performance requirement.

Timber frame:

Density (kg/m³)

R-value:

Thickness:

Size:

14.0

R2.0

75 mm

580 mm x 1160 mm

20.0

R2.6

90 mm

430 mm x 1160 mm