5313KL
RONDO SYSTEMS - PLASTERBOARD & SHEET CEILINGS
1
GENERAL

If you have pre-customised this work section using the "questions and answers" provided as part of the downloading process, it may be necessary to amend some clauses to suit the final project-specific version.

The section must still be checked and customised to suit the project being specified, by removing any other irrelevant details and adding project-specific details and selections.

 

This section relates to the supply and installation of Rondo Ceiling Systems.  It includes;

Modify / expand this clause to suit requirements of the final version of the section.

 

This section refers to a concealed suspension or direct fixed furring channel system supporting screw-fixed flush-finished plasterboard or other sheet material.

 

Rondo Building Services Pty Ltd offer an engineering design service, delivering project specific documentation prior to consent and tender.  A detailed wind and seismic report as part of the consultant supplied information may be required in order to undertake a design.

If required a PS1 from an independent engineer can be provided for a fee, this process is facilitated by Rondo.  By contacting Rondo through the Masterspec work section support function, the design service can be coordinated with this specification section and other consultant documentation.  Rondo project specific documentation can be attached within the specification Contract Appendix.

 

The ceiling manufacturer/supplier will require some detailed project information to enable their specific design of the ceiling system. Ensure the information is available in this specification and/or on the drawings (for instance ceiling height etc.).

Refer to AS/NZS 2785, Appendix B for a list of typical project information required.

 

The Rondo project specific documentation provides a similar level of documentation to shop drawings.  Shop drawings can be provided if the design service is not required.

1.1
RELATED WORK

Refer to ~ for ~

Delete if no sections.

Include cross references only to other work sections where they include directly related work.  The  Rondo XPRESS® Drywall Grid Ceiling System is compatible with the Rondo DONN® Exposed Grid Ceiling System.  Refer to:

5311RT RONDO SYSTEMS - TILE CEILINGS for the supply and installation of Rondo DONN® Exposed Grid Ceiling System.

5316 DIRECT-FIX GRID SYSTEM FOR SHEET CEILINGS for simple residential type metal grid and sheet lined ceilings.

1.2
ABBREVIATIONS AND DEFINITIONS

Refer to the general section 1232 INTERPRETATION & DEFINITIONS for abbreviations and definitions used throughout the specification.

 

The following abbreviations apply specifically to this section:

AWCINZ

Association of Wall and Ceiling Industries of New Zealand Inc

Refer to general section 1232 INTERPRETATION & DEFINITIONS for abbreviations used throughout the specification.

Documents
1.3
DOCUMENTS

Refer to the general section 1233 REFERENCED DOCUMENTS.  The following documents are specifically referred to in this section:

NZBC B1/VM1

Structure general

NZBC B2/AS1

Durability

AS/NZS 1170.0

Structural design actions - General principles

AS/NZS 1170.1

Structural design actions - Permanent, imposed and other actions

AS/NZS 1170.2: 2011

Structural design actions - Wind actions

NZS 1170.5

Structural design actions - Earthquake actions - New Zealand

AS/NZS 2588

Gypsum plasterboard

AS/NZS 2785

Suspended Ceilings - Design & Installation

NZS 4219

Seismic performance of engineering systems in buildings

NZS 4541

Automatic fire sprinkler systems

AS/NZS 4600:2005

Cold formed steel structures

AS 1397

Continuous hot-dip metallic coated steel sheet and strip - Coatings of zinc and zinc alloyed with aluminium and magnesium

AS/NZS 4600:2005 Amendment 1 is cited by NZBC, but AS/NZS 4600:2018 has not at the time of writing been cited by NZBC. This section uses the 2005 Amendment 1 version as an Acceptable Solution; consult with the BCA as to their requirements if you want to use the 2018 version as an Alternative Solution.

 

 Note: AS/NZS 1170.2:2011 is cited in       NZBC B1/VM1 Structure at the time of writing. The new version       AS/NZS 1170.2:2021 is not yet cited. Amend the section by removing the year reference if using the 2021 version and amend the section accordingly.

 

Delete from the DOCUMENTS clause any document not cited.  List any additional cited documents.

The following are related documents and if referred to in the work section need to be added to the list of DOCUMENTS.

NZBC E2/AS1

External moisture

1.4
MANUFACTURER/SUPPLIER DOCUMENTS

Manufacturer and supplier documents relating to this part of the work:

Rondo Professional Design Manual

Rondo KEY-LOCK® installation guide

Rondo XPRESS® Drywall Grid System Rondo brochure

Rondo Steel Stud Drywall Concealed Ceiling System in Design Guide

Certificate of Licence for New Zealand Made trademark - Licence No. 806965

List documents relating to this part of the work, i.e. technical product/system specifications, test reports, appraisals, certification, etc. Normally they will be referred to in the text by the abbreviated title.

 

Manufacturer/supplier contact details

Company:

Rondo Building Services Pty Ltd

Web:

www.rondo.co.nz

Email:

steve.hardy@rondo.co.nz

Telephone:

09 636 5110

It is important to ensure that all personnel on site have access to accurate, up to date technical information on the many products, materials and equipment used on a project.  In most cases individual products are not used in isolation, but form part of a building process. Also a particular manufacturer's and/or supplier's requirements for handling, storage, preparation, installation, finishing and protection of their product can vary from what might be considered the norm. Access to technical information can help overcome this potential problem.

Warranties
1.5
WARRANTY - MANUFACTURER/SUPPLIER

Provide a material manufacturer/supplier warranty:

10 years

For Rondo branded products against defects in materials under normal use.

In addition, Rondo warrants that the Rondo KEY-LOCK® Suspended Ceiling Systems will remain structurally sound for a period of 15 years.

 

  • Provide this warranty on the manufacturer/supplier standard form
  • Commence the warranty from the date of purchase.

 

Refer to the general section 1237 WARRANTIES for additional requirements.

Modify or expand the clause to suit project or manufacturer/supplier requirements, options include:

  • Modify the form to be used
  • Commence the warranty from the date of purchase (check with the manufacturer/supplier)
Requirements
1.6
QUALIFICATIONS GENERALLY

Refer to 1270 CONSTRUCTION for requirements relating to qualifications.

Provide evidence of experience, listing completed projects of similar size and complexity.

Delete clause if using QUALIFICATIONS WORKERS - INDUSTRY QUALIFICATIONS REQUIREMENTS.

1.7
QUALIFICATIONS WORKERS – INDUSTRY QUALIFICATION REQUIREMENTS

Installation by a manufacturer accredited installer, using the manufacturer technical services.  Installers are to be members of the AWCINZ.  Refer to 1270 CONSTRUCTION for additional requirements relating to qualifications.

Provide evidence of experience, listing completed projects of similar size and complexity.

Delete clause if using QUALIFICATIONS GENERALLY.

For a simple direct fix grid, this clause may not be needed.

1.8
NO SUBSTITUTIONS

Substitutions are not permitted to any of the specified systems, components and associated products listed in this section.

1.9
SAMPLES

Refer to the general section 1270 CONSTRUCTION for details of how samples will be reviewed and how instructions to proceed will be given.  Provide the following samples for review:

 

Sample A

Sample B

Sample C

Sample description:

~

~

~

Sample type:

~

~

~

Number:

~

~

~

Location:

~

~

~

Supporting documentation:

~

~

~

Reviewer:

Contract administrator

~

Contract administrator

~

Contract administrator

~

Time for review:

10 working days ~

10 working days ~

10 working days ~

Review criteria:

~

~

~

The intention of this clause is to allow samples to be obtained that are not otherwise readily available to a reviewer.

 

Delete rows and columns not required or add "n/a".

Sample description:

Describe the sample, size etc.

Allow to erect a sample section of the suspended ceiling system.  Subject to confirmation in writing, the sample section may form part of the completed installation.

Amend or expand this clause as appropriate to the project, including requirements for incorporating other elements - luminaires, diffusers, surrounding surfaces - into the sample section.

Sample type:

Portable sample for review

Portable control sample

Fixed sample for review

Fixed control sample

 

Control samples define requirements for type and quality and are used for comparison purposes throughout the contract.

 

A "portable" sample is a sample that is easily movable, convenient for carrying. A "fixed" sample is a sample (semi) permanently placed. Expand on these terms as necessary.

Number:

State number of samples required, e.g. a minimum of three control samples - portable allow a sample to be retained on site with the other samples retained by the contract administrator and contractor.

Location:

Identify location of fixed samples, e.g. off site, on site, in situ

Supporting documentation:

Describe any additional documents required to support the review.

Reviewer:

 

Modify to suit the project, add additional reviewers if required.

Time for review:

Alter time if required.  Expand to state timing in relation to when and where the sample is provided, e.g. at first site meeting.

Review criteria:

For example:

- Appearance

- Texture

- Colour

Add any critical items. Provide clarity for work that is not dependent on the review to continue.

1.10
RONDO SPECIFIC DESIGN DOCUMENTS

Refer to SELECTIONS for project specific design documentation by Rondo Building Services Pty Ltd, generally consisting of:

  • Design calculations
  • Dimensioned plans/elevations of elements
  • Details of construction, connections and support systems
  • Dimensions of all typical elements
  • Jointing details and method of fixing between individual elements and between this installation and adjacent work
  • Provision for thermal and seismic movement
  • Bracing requirements, due to wind and seismic loads
  • A schedule of materials, finishes and componentry

Rondo Building Services Pty Ltd offer an engineering design service, delivering project specific documentation prior to consent and tender as an alternative to the Shop Drawing process.  A detailed wind and seismic report as part of the consultant supplied information may be required in order to undertake a design.

 

By contacting Rondo through the Masterspec work section support function, the design service can be coordinated with this specification section and other consultant documentation.  Rondo project specific documentation can be attached within the specification Contract Appendix.

1.11
SHOP DRAWINGS

Refer to the general section 1235 SHOP DRAWINGS for the requirements for submission and review and the provision of final shop drawings.

 

Provide shop drawings to show the general arrangement including, but not be limited to:

  • Design calculations.
  • Fully dimensioned elevations of all elements
  • Complete details of construction, connections and all support systems
  • Dimensions of all typical elements
  • Jointing details and method of fixing between individual elements and between this installation and adjacent work
  • Provision for thermal movement
  • Provision for seismic movement and movement under prevailing wind loads
  • Bracing requirements, due to wind and seismic loads (indicate any design and construction work by others, to meet these requirements)
  • Sequence of installation
  • Co-ordination requirements with other work
  • A full schedule of materials, finishes and componentry

The general section 1235 SHOP DRAWINGS describes the process of submission and review of shop drawings.  Use this clause to describe the specific requirements of what the required shop drawings are to include.

 

Rondo Building Services Pty Ltd offer an engineering design service, delivering project specific documentation prior to consent and tender as an alternative to the Shop Drawing process.

 

By contacting Rondo through the Masterspec work section support function, the design service can be coordinated with this specification section and other consultant documentation.  Rondo project specific documentation can be attached within the specification Contract Appendix.

 

Rerun the Q&A if required to obtain the Rondo design service clause content.  Delete this clause if using the Rondo design service.

1.12
AS BUILT DOCUMENTS

Refer to the general section 1238 AS BUILT DOCUMENTATION for the requirements for submission and review of as built documents and records.

 

Provide the following as built documents and records:

~

  • Provide draft as built information prior to practical completion.
  • Provide final as built information prior to the end of the defects liability period.

The general section 1238 AS BUILT DOCUMENTATION describes the process of submission and review of as built documentation.

Use this clause to describe the specific requirements of what the required as built documents are to include.

Compliance information
1.13
INFORMATION REQUIRED FOR CODE COMPLIANCE

Provide the following compliance documentation:

  • Manufacturer / supplier warranty.
  • Internal Rondo engineered design - refer to SELECTIONS.
  • Producer Statement (PS1) - Design from supplier independent engineer.
  • Producer Statement (PS3) - Construction from the applicator / installer.
  • Producer Statement (PS4) - Construction Review from an acceptable suitably qualified person.
  • Other information required by the BCA in the Building Consent Approval documents.

Producer Statement - Design (PS1) required from consultants to be engaged by the Contractor. May involve a fee, check with supplier.
Producer Statement - Construction (PS3) required from installers as a condition of carrying out this work.
Producer Statement - Construction Review (PS4) required from consultants to be engaged by the Contractor.
A PS1 from an independent engineer can be provided for a fee.  Rondo are willing to facilitate this process

1.14
PRODUCER STATEMENT - DESIGN

Refer to SELECTIONS for an independent Producer Statement - Design (PS1).

A PS1 from an independent engineer can be provided for a fee.  Rondo are willing to facilitate this process.

Performance

This clause is setting a standard of performance for design by the contractor, to meet.  Specifiers should therefore consider adding some means of confirming (say by testing or certification) that the performance criteria will be or has been met.

Ensure correct information is supplied in 1220 PROJECT.

Use the following clause whether specifying by performance or not.

1.15
LOADING CODE REQUIREMENT

To AS/NZS 2785, comply with the requirements of; AS/NZS 1170.0, AS/NZS 1170.1, AS/NZS 1170.2, NZS 1170.5, NZBC B1/VM1, as appropriate.

Load combinations are considered in accordance with AS/NZS 1170.0

In some seismic areas the connection details may not be valid.  Refer to Rondo Building Services Pty Ltd for advice.

1.16
CERTIFICATION

Provide:

  • Certificates and other evidence that the system complies with the standards of performance specified.
  • Producer Statements.
1.17
FIRE RATING REQUIREMENT

Design the ceiling system so that together with the floor and ceiling lining system, it is to NZBC C/AS1 - AS2, Appendix C, 5.1 Fire Resistance.  Refer to SELECTIONS.

Delete this clause if it does not apply, not all systems can provide a FRR.

Note here the floor system and ceiling lining are specified elsewhere.

Modify to suit project requirements.

1.18
ENVIRONMENTAL REQUIREMENTS

Durability to NZBC B2/AS1.

Performance - Wind (design by contractor)

This clause is setting a standard of performance to be met by the contractor.  Specifiers should therefore consider adding some means of confirming (say by testing or certification) that the performance criteria will be, or has been met.

Ensure correct information is supplied in 1220 PROJECT.

1.19
DESIGN PARAMETERS WIND - DESIGN BY CONTRACTOR

Design the installation to the wind pressure parameters of AS/NZS 1170.2.  Refer to general section 1220 PROJECT for general details.

Contact Rondo Building Services Pty Ltd for their internal engineering design service or to facilitate Producer Statement - Design (PS1).

Refer to SELECTIONS specific design performance requirements.

Obtain information from the project structural engineer.

Delete the clause if it does not apply and the contractor is not expected to design.

Rondo Professional Design Manual references AS/NZS 1170.2.

Performance - Seismic (design by contractor)

This clause is setting a standard of performance for design by the contractor, to meet.  Specifiers should therefore consider adding some means of confirming (say by testing or certification) that the performance criteria will be or has been met.

Ensure correct information is supplied in 1220 PROJECT.

1.20
SEISMIC - SPECIFIC DESIGN

Design the system and its anchorages/fixings to resist the earthquake loads of the seismic zone in accordance with NZS 1170.5.  Refer to general section 1220 PROJECT for general details.  Contact Rondo Building Services Pty Ltd for their internal engineering design service or to facilitate Producer Statement - Design (PS1).

Refer to SELECTIONS specific design performance requirements.

Obtain information from the project structural engineer.

Delete the clause if it does not apply and the contractor is not expected to design.

Rondo Professional Design Manual references NZS 1170.5.

Quality control and assurance
1.21
INSPECTIONS

~

Use this clause for parts of the work where;

 

Special arrangements are required for notification for inspections.

These inspections may include 'Hold Points' or 'Notification Points'.

Hold Point:

Work may not proceed until the work in question has been inspected.

Notification Point:

Work may proceed, but with the Contract Administrator being given sufficient notice of this so that they can arrange to observe the work in progress, or not to observe it, as the case may be.

or

the manufacturer/supplier is required to carry out inspections outside their normal activities and provide reports or other documents in support of the work carried out.

or

the Contractor is required to carry out or engage consultants to carry out inspections of parts of the work.  It will typically be expected that the person carrying out the inspections will be required to provide producer statements in support of the work carried out.

2
PRODUCTS
Suspension system - Rondo KEY-LOCK suspended ceiling system

Refer to Rondo for design assistance and advice.

2.1
KEY-LOCK SUSPENDED CEILING SYSTEM

KEY-LOCK suspended ceiling system to AS/NZS 2785, hot-dip galvanized steel elements manufactured from G2 steel strip to AS 1397 including furring channels and snap in sections.  Primary (Top Cross Rail) and secondary components (Furring Channel).

Rondo KEY-LOCK offers a system of top cross rails, furring channels, battens and clips, allowing for a range of spans and suspension point spacings.  The systems can be used in both fire rated and non fire rated suspended ceilings, eaves linings, direct fixed battens and bulkhead installations.

KEY-LOCK Ceiling System can also be installed with Acoustic Mounts.

Can also produce profiles in custom lengths and radii for curved ceilings.

Individual projects may require specialist detailing and development.

State if the system is to be fire-rated.

2.2
SEISMIC RESTRAINT

To AS/NZS 2785, 4.3.3 Seismic Restraint Types and/or suitable proprietary back braces for ceiling systems.

Note: Non-structural partition walls are not recommended as seismic restraints, unless specifically designed to do so.

Direct-fix ceiling system - Rondo KEY-LOCK direct-fix ceiling system
2.3
KEY-LOCK DIRECT FIX CEILING SYSTEM

KEY-LOCK direct fix ceiling system to AS/NZS 2785, including suspension depths of up to 200mm.
Furring channels, Direct fix clips for fixing to timber, steel and concrete, to carry ceiling sheets, light fixtures and air distribution elements to comply with NZS 1170.5.
Provide diagonal bracing to provide lateral stability if required.  Perimeter trim, expansion joints and seismic joints etc. to AS/NZS 2785, as required.
Hot-dip galvanized steel elements manufactured from steel strip to AS 1397.

Rondo KEY-LOCK offers a system of furring channels, battens and clips, allowing for a range of spans and suspension point spacings.
The systems can be used in both fire rated and non fire rated suspended ceilings, eaves linings, direct fixed battens and bulkhead installations.
KEY-LOCK Ceiling System can also be installed with Acoustic Mounts. Can also produce profiles in custom lengths and radii for curved ceilings. Individual projects may require specialist detailing and development.
Note: Non-structural partition walls are not recommended as seismic restraints, unless specifically designed to do so.
Ensure that hybrid systems of combined suspended and direct fixed systems are carefully considered for movement..

2.4
PRIMARY SECTIONS

Rondo 25mm or 38mm top cross rail to AS 1397.  Steel grade and zinc coating class G2 Z275 to AS 1397.

G2 refers to a steel grade designation under formability grades, Z275 refers to a zinc coating class with a coating mass of 275g/m².

2.5
FURRING BATTEN SECTIONS

Rondo 16mm, 28mm, or 35mm furring/batten sections to AS 1397.  Steel grade and zinc coating class G2 Z275 to AS 1397.

G2 refers to a steel grade designation under formability grades, Z275 refers to a zinc coating class with a coating mass of 275g/m².

Components

Refer to Rondo for design assistance and advice.

2.6
DIRECT FIX CLIPS

Hot-dip galvanized steel elements manufactured from steel strip to AS 1397.

Individual projects may require specialist detailing and development.

2.7
SECTION JOINERS

Hot-dip galvanized steel elements manufactured from steel strip to AS 1397.

2.8
RONDO WALL TRIM

Rondo wall trim sections to AS 1397.  Steel grade and zinc coating class G2 Z275 to AS 1397.

G2 refers to a steel grade designation under formability grades, Z275 refers to a zinc coating class with a coating mass of 275g/m².

2.9
RONDO SUSPENSION RODS, BRACKETS CLIPS, RODS & ANCHORS

Rondo components to AS 1397.  Steel grade and zinc coating class G2 Z275 to AS 1397.

Accessories

Refer to Rondo for design assistance and advice.

2.10
FASTENERS SUSPENSION SYSTEM

Pop rivets or 8g-16 x 12mm (minimum) self drilling wafer head screws to join furring channels and C channels as detailed in Rondo Professional Design Manual and to Rondo Building Services Pty Ltd requirements.

2.11
FASTENERS DIRECT FIX

8g-16 x 25mm (minimum) self drilling wafer head screws for fixing to timbers detailed in Rondo Professional Design Manual and to Rondo Building Services Pty Ltd requirements.

2.12
SCREWS

25mm x 6 gauge non-rusting Type S self-drilling and self-tapping bugle head screws as detailed in Rondo Professional Design Manual and to Rondo Building Services Pty Ltd requirements.

Rondo XPRESS® Drywall Grid System

Refer to Rondo for design assistance and advice.  Suitable for:

  • Concealed ceiling systems
  • Plasterboard, fibrous plaster and fibre
  • Direct fix or fully suspended applications
  • Seamless transitions from concealed to exposed grid ceilings
  • Bulkhead and boxed soffits
  • Corridors , without the use of suspension hangers
  • Fire-rated applications
  • Seismic requirements
  • Acoustic requirements

This system is compatible with Rondo DONN® Exposed Grid Ceiling System.  Refer to:

5311RT RONDO SYSTEMS - TILE CEILINGS for the supply and installation of Rondo DONN® Exposed Grid Ceiling System.

2.13
RONDO XPRESS® DRYWALL GRID SYSTEM

Rondo XPRESS® Drywall Grid System to AS/NZS 2785, hot-dip galvanized steel, Z275 finish.

2.14
MAIN TEES

38mm deep with 24mm and 38mm face width options in standard and heavy duty gauges, refer to SELECTIONS.

2.15
CROSS TEES

38mm deep with 24mm and 38mm face width options, refer to SELECTIONS.

2.16
WALL TRIMS

Refer to SELECTIONS.

2.17
CLIPS

Refer to SELECTIONS.

Components
2.18
SUSPENSION CLIPS, BRACKETS, RODS & WIRE

Refer to SELECTIONS.

Accessories
2.19
FASTENERS

Pop-rivet, Tek® Screws, XDSC Clip

Materials - Rondo Steel Stud Drywall Ceiling System
2.20
STEEL STUD SECTIONS

Rondo stud sections to AS/NZS 4600.  Steel Grade and zinc coating class G2 Z275 to AS 1397 with preformed service holes to stud webs and a range of BMT options.  Refer to SELECTIONS for type.

This system is used to achieve greater spanning distances than KEY-LOCK and/or when it is difficult to install a suspended system.

G2 refers to a steel grade designation under formability grades, Z275 refers to a zinc coating class with a coating mass of 275g/m².

 

Available in a range of widths (51mm, 64mm, 76mm, 92mm & 150mm) and BMT options (0.50, 0.55, 0.75 & 1.15).  Studs are designed to friction fit into tracks, with options for staggered studs within a larger track section for acoustic rated walls.

2.21
STEEL TRACK SECTIONS

Rondo track sections to AS/NZS 4600.  Steel Grade and zinc coating class G2 Z275 to AS 1397 with a range of widths and BMT options.  Refer to SELECTIONS for type.

Tracks accommodate the friction fitting of studs into the track system.  The tracks hold the studs in position until the lining board is fitted and also allow a slip joint for movement in the structure, for this reason the lining is not fixed into the track section unless specifically stated / detailed.

 

Options include standard wall tracks, flexible wall tracks, deflection head tracks and slotted deflection head tracks.  There is no requirement to isolate the track sections from a slab unless specifically stated.  Track sections are nominally 3000mm long.

2.22
MECHANICAL JOINTS

Joint Type:

Fastener:

Type 1 (spans up to 3.0m or 2 or 3 span ceilings up to 4.0m)

1/#8-18 x 16mm wafer head tek screw in 2 places

Type 2 (spans larger than 3.0m)

2/#10-16mm tek screws

Type 3 (spans larger than 3.0m)

3/#10-16mm tek screws

Mechanical joints are used where the spans of the ceiling joists exceed those allowable for friction joints.

2.23
SUSPENSION JOINT TYPE 1

30mm x 0.8mm hoop iron strapping wrapped around underside of purlin and fixed to web with 2/#8-18 x 16mm wafer head tek screws each side of purlin and screws.

2.24
SUSPENSION JOINT TYPE 2

Rondo angle bracket 553 fixed to purlin with 2/#8-18 x 16mm wafer head tek screws in 4 places.

2.25
SUSPENSION JOINT TYPE 3 - CONCRETE SOFFIT

Rondo angle bracket 247 fixed to stud with 2/#8-18 x 16mm tek screws and bracket fixed to concrete soffit with proprietary masonry anchor.

Use when connecting to concrete soffits.

Lining and Insulation
2.26
PLASTERBOARD

Gypsum plaster core encased in a face and backing paper formed to AS/NZS 2588.  Refer to SELECTIONS for type and thickness.

Expand this clause to cover a range of plasterboard types, or delete and cross reference to other work sections.

2.27
LINING BOARD

Refer to SELECTIONS for type, thickness and finish.

Delete or expand this clause to cover a range of lining board types, or delete and cross reference to other work sections.

2.28
INSULATION

Refer to SELECTIONS for type and thickness.

Complete this clause to cover a range of insulation types or delete and cross reference to other work sections.

Access Panels
2.29
ACCESS PANEL

Refer to SELECTIONS.

Rondo PANTHER® Access Panel Systems are designed for internal installation to provide access to services.

3
EXECUTION
Conditions
3.1
DELIVERY, STORAGE & HANDLING OF PRODUCTS

Refer to 1270 CONSTRUCTION for requirements relating to delivery, storage and handling of products.

Use this standard generic clause and if appropriate add additional special requirements.

3.2
ROUTINE MATTERS

Refer to 1250 TEMPORARY WORKS & SERVICES for protection requirements.

Refer to 1270 CONSTRUCTION for requirements relating to defective or damaged work, removal of protection and cleaning.

Use this standard generic clause and if appropriate add additional special requirements.

3.3
SUBSTRATE

Ensure substrate is plumb, level and in true alignment.  Do not start erection if the substrate will not allow work of the required standard.  Complete any remedial work found necessary before framing erection.

3.4
COMMENCING THIS WORK

Commencing this work means the substrate is accepted as allowing work of the required standard.

3.5
CO-ORDINATE SERVICES

Co-ordinate and co-operate with electrical and mechanical work to avoid conflict between suspension members and luminaires, diffusers, pipework and ducting. Confirm the provision of extra hangers and fixings.
Ensure co-operation with work in and above the ceiling, including the marking of specific ceiling tiles below major access points to above-ceiling services. Colour coded markings to follow the standards laid down by mechanical and electrical services.
Services and other attachments, attached to or supported by the ceiling grid system to AS/NZS 2785, ensure that:

  • items over 7.5kg and items under 7.5kg but falling greater than 3m, require a tether to AS/NZS 2785, anchored to structure.
  • items attached to the ceiling grid must be under 10kg mass, items over 10kg cannot be attached to the grid and must be independently supported.
  • unless designed otherwise, the ceiling systems total load of services and other attachments must not exceed 3kg/m².
  • light fittings installed to AS/NZS 2785 and NZS 4219.
  • ceiling system clearances to structure and services etc. that are not attached to the ceiling system, to be to NZS 4219, and/or NZS 4541 for sprinklers.

Confirm loadings with manufacturer.

Note - Although items under 10kg mass are allowed, it is recommended that 7.5kg should be considered as a maximum for attaching to the grid under ULS conditions.

Direct fixed systems may be able to vary loads slightly from the above depending on fixing centres and lining capacity, discuss with manufacturer.  Also with direct fixed systems, subject to design, small lightweight light fittings may be able to be fixed to the lining (for recessed) or lining back support (for pendants).

3.6
SITE CONDITIONS

Do not begin installation until the building is closed in, fully glazed, the roof watertight, and mechanical and electrical duct work above the ceiling completed.  To AS/NZS 2785, Appendix C, site Conditions, Installation and Inspections.

If fast track construction is used, this may not be possible and tiles must be selected accordingly.

Installation generally
3.7
STANDARDS AND TOLERANCES

Refer to the general section 1270 CONSTRUCTION for general requirements.

Amend this clause to describe specific standards and tolerances to be achieved in carrying out this part of the work.  Although such tolerances are typically included in standards (NZS, AS/NZS etc) in certain circumstances it is worth restating these in this clause.

3.8
SETTING OUT

Set out the framing work true to line and square before starting erection.

3.9
INSTALL

Installation to AS/NZS 2785 minimum standards, and the systems Rondo Professional Design Manual and Rondo Building Services Pty Ltd requirements.

 

Allowance for support members:

  • Space required by the loads on the system and the type of ceiling.
  • For the installation of services and accessories, including ductwork, light fittings and diffusers.
  • Additional back support or suspension members for the fixing of services and accessories to prevent distortion, overloading or excessive vertical deflection.
  • For access for maintenance of services.

 

Allowance for a ceiling system where failure of any one suspension point does not cause a progressive failure of the ceiling.
Allowance for height adjustment with a length adjustment device at each suspension point, permitting length variation of at least 50mm.

 

If required, allow for notch grid members at the junction with the perimeter trim to make sure the ceiling lining lies flat on the perimeter trim. Do not attach the suspension system to the lip or flange of purlins.

 

Fix, erect and fit to finish rigid, plumb, square and true to line and face.  Where components required cutting on site, use metal snips, fine-toothed band or hack saws.  Adjust all suspension systems and clips by laser level until they are all level.  Hangers and bracing are not to be fixed closer than 150mm to plenum building services.

 

Install all movement joints required.

 

Services support to conform to the following:

  • If the service has not been designed to accept the ceiling load, do not fix suspension members to services (e.g. ductwork).
  • If services obstruct the ceiling supports, provide bridging and suspension on each side of the services.
  • Do not support services terminals on ceiling lining, unless specified.
3.10
BULKHEADS

Form bulkheads to manufacturer requirements.  Diagonally brace at regular intervals to provide lateral stability.  In addition to the dead load of the bulkhead, all bulkheads should be designed for the following minimum loads:

  • 0.25 kPa laterally.
  • 0.15 kPa vertically.

Confirm with Manufacturer/supplier or Structural Engineer.

3.11
INSTALL SEISMIC RESTRAINTS

Install ceiling system seismic restrains and bracing as required to prevent lateral movement and resist the imposed horizontal seismic force, to AS/NZS 2785.

If ceiling systems abut glazing, the horizontal seismic forces generated by the ceiling can damage the glazing.

If large runs of ceilings are terminated at bulkheads, the horizontal seismic forces generated by the ceiling can cause separation between the ceiling and bulkhead if not properly designed.

If the ceiling is terminated at a partition, design the partition for the seismic force generated by the ceiling.

If the partition is terminated at the ceiling, design for the seismic force generated by the partition.

3.12
PENETRATIONS

To AS/NZS 2785 and NZS 4219 generally, with sprinkler systems to NZS 4219 and/or NZS 4541.

Accommodate recessed light fittings, air conditioning outlets and other electrical and/or mechanical services that are fixed to or pass through the ceiling system.  Provide independent support for these as necessary.

Modify clause to suit project requirements.

3.13
ISOLATE

Isolate dissimilar metals with neoprene sheeting, tape or pipe lagging.

3.14
INSULATION

Install insulation to insulation manufacturer and Rondo Building Services Pty Ltd requirements.

Expand/modify clause to suit project requirements.

3.15
LINING

Fix and finish lining boards to manufacturer and Rondo Building Services Pty Ltd requirements.

Install services before lining.  Stagger sheet joins.

Delete when cross referencing to other sections, incorporate requirements in the separate section.  Modify this clause to suit.

3.16
ACCESSIBILITY

Provide access to the ceiling system and the in-ceiling and above-ceiling services so that maintenance and removal of any part can be carried out without damage to the ceiling system or panels.

As full access in all areas is clearly impractical, any special requirements for clear access will need to be defined; either by description here, or on the drawings.

3.17
ACCESS PANEL

Install to Rondo Panther installation requirements.

3.18
INSTALLATION - SPECIFIC

Refer to SELECTIONS for Rondo Building Services Pty Ltd project specific design documentation.

3.19
PROTECT EXISTING WORK

Protect adjacent existing work from damage during the installation.

Installation - Rondo KEY-LOCK Ceiling System
3.20
INSTALLATION

Install the Rondo KEY-LOCK suspension system to AS/NZS 2785, and the Rondo Professional Design Manual and KEY-LOCK® installation guide.

Screw-fix sheets to furring channel sections at the centres required by the ceiling lining manufacturer.  Stagger joints and fully support on furring sections and primary sections at centres to suit the load and Rondo installation manual.

Refer to 5113 PLASTERBOARD LININGS for plasterboard and stopping specification.

Installation - Rondo XPRESS® Drywall Grid System
3.21
INSTALLATION

Install the Rondo XPRESS® Drywall Grid System to AS/NZS 2785, Rondo Professional Design Manual, Rondo XPRESS® Drywall Grid System Rondo brochure and Rondo Building Services Pty Ltd requirements.

Installation - Rondo Steel Stud Drywall Ceiling System
3.22
INSTALLATION - GENERAL

Installation to Rondo® Steel Stud Drywall Framing Systems Steel Framing Installation Guide, Rondo Professional Design Manual and Rondo Building Services Pty Ltd requirements.  Fix, erect and fit to finish rigid, plumb, square and true to line and face.

3.23
INSTALLATION - STEEL STUD DRYWALL CEILING SYSTEM

Installation to Rondo Professional Design Manual and Rondo Building Services Pty Ltd requirements.

3.24
BRIDGING TRACK SECTIONS

Fit bridging in position with fasteners in accordance with the Rondo Professional Design Manual.

Completion
3.25
COMPLETION MATTERS

Refer to 1270 CONSTRUCTION for completion requirements and if required commissioning requirements.

Use this standard generic clause and if appropriate add additional special requirements.

4
SELECTIONS

For further details on selections go to www.rondo.co.nz

Substitutions are not permitted.

Select the options to suit the project and delete options not specified.

4.1
FIRE RATED SYSTEMS

Location:

~

FRR:

~ / ~ / ~ minutes

Note here if the floor system is specified elsewhere.

4.2
ACOUSTIC RATED SYSTEMS

Location:

~

STC:

~

Delete when cross referencing to other sections.

Performance - Wind (design by contractor)
4.3
DESIGN PARAMETERS WIND - DESIGN BY CONTRACTOR

Wind design and performance criteria to AS/NZS 1170.2 as follows:

Parameter

Wind

Design wind speed (Vdes.Ø)

~ m/s

Terrain Category (Mz,cat)

~

Shield Factor (Ms)

~

Topographic multiplier (Mt)

~

Hill-shape multiplier (Mh)

~

Lee multiplier (Mlee)

~

Internal pressure coefficient (Cp,i)

~

Fill in project values, obtain information from the project structural engineer.

These values come are critical to allow the Contractor to design the ceiling accurately.

Usually design for wind is only required if there are opening external windows/doors or other sources of wind pressure differential (including some roof spaces).

Ensure that all other generall information is available in this specification or on the drawings (for instance ceiling height etc.). Refer to AS/NZS 2785, Appendix B for further information required.

Delete the clause if it does not apply and the contractor is not expected to design.

Performance - Seismic (design by contractor)
4.4
DESIGN PARAMETERS SEISMIC - DESIGN BY CONTRACTOR

Seismic design and performance criteria to NZS 1170.5 as follows:

 

Parameter

Value

Building Importance Level

~

Design Working Life

~ years

Site Sub-soil Class

~

Near Fault Factor N(T,D)

~

Part Classification Category (P1-P7)

~

Interstorey Drift - ULS

~ mm

Interstorey Drift - SLS

~ mm

Fill in project values, obtain information from the project structural engineer.

These values are critical to allow the Contractor to design the ceiling accurately.

Ensure that all general information is available in this specification or on the drawings (for instance ceiling height etc.). Refer to AS/NZS 2785, Appendix B for typical information required.

Delete the clause if it does not apply and the contractor is not expected to design.

4.5
SEISMIC RESTRAINT

Location:

~

Brand:

~

Type:

~

Material:

~

Delete Brand if not a proprietary type.

Design documentation
4.6
RONDO SPECIFIC DESIGN

Document:

~

Submitted:

~

Available:

~

Document:

Identify Rondo specific design documents

Submitted:

Building consent, tender (or both)

Available:

Specification Contract Appendix, or describe alternative.

4.7
PRODUCER STATEMENT - DESIGN

PS1:

~

Available:

~

A PS1 from an independent engineer can be provided for a fee, this process is facilitated by Rondo.

PS1:

Identify the producer statement - design (PS1)

Available:

Specification Contract Appendix, or describe alternative.

Rondo KEY-LOCK Ceiling System
4.8
RONDO KEY-LOCK SUSPENDED CEILING SYSTEM

Location:

~

Type/Brand:

KEY-LOCK Suspended Ceiling System

FRR:

~

Acoustic Mounts:

~

Curved radius:

~

Top Cross Rails (TCR):

~

Furring Channels (FC):

~

TCR to FC Joiners:

~

Perimeter Trims:

~

Suspension Brackets & Clips:

~

Lining Configuration/Pattern:

~

FRR:

Delete if not required

 

Acoustic mounts:

Contact Rondo Building Services Pty Ltd, delete if not required.

 

Curved radius:

Nominate for curved ceiling, Delete if not required.

 

Top Cross Rails (TCR):

#127 (25mm deep)

 

 

#128 (38mm deep) - For fire rated solutions

 

Furring Channels (FC):

#129 (28mm deep)

 

 

#155 (28mm deep) - 48mm wide, enabling negative board joint detail.

 

 

#308 (16mm deep)

 

TCR to FC Joiners:

#139 (for 127 & 128 to 129 & 308)

 

 

#159 (for 127 & 128 to 155)

 

Perimeter Trims:

#141 Seismic Heavy Duty Channel to suit 129 (28mm)

 

 

#140 Channel to suit 129 (28mm)

 

 

#142 Channel to suit 308 (16mm)

 

 

#P51 Shadowline Set Bead for 10mm board

 

 

#P52 Shadowline Set Bead for 13mm board

 

 

#P53 Shadowline Set Bead for 16mm board

 

 

Note: a Shadowline detail is more likely to provide a better long term solution against cracking than square stopping.

 

Suspension Brackets & Clips

To suit substrate and component selection, Contact Rondo Building Services Pty Ltd

 

4.9
RONDO KEY-LOCK DIRECT FIX CEILING SYSTEM

Location:

~

Type/Brand:

KEY-LOCK Direct Fix Ceiling System

FRR:

~

Acoustic Mounts:

~

Curved radius:

~

Furring Channels (FC):

~

Perimeter Trims:

~

Fasteners direct fix:

~

FRR:

Delete if not required

 

Acoustic mounts:

Contact Rondo Building Services Pty Ltd, delete if not required.

 

Curved radius:

Nominate for curved ceiling, Delete if not required.

 

Furring channels (FC):

#308 (16mm deep)

 

 

#129 (28mm deep)

 

 

#155 (28mm deep) - 48mm wide, enabling negative board joint detail.

 

Perimeter Trims:

#141 Seismic Heavy Duty Channel to suit 129 (28mm)

 

 

#140 Channel to suit 129 (28mm)

 

 

#142 Channel to suit 308 (16mm)

 

 

# P51 Shadowline Set Bead for 10mm board

 

 

# P52 Shadowline Set Bead for 13mm board

 

 

# P53 Shadowline Set Bead for 16mm board

 

 

Note: a Shadowline detail is more likely to provide a better long term solution against cracking than square stopping.

 

Fasteners direct fix:

To suit substrate and component selection, Contact Rondo Building Services Pty Ltd

 

4.10
RONDO KEY-LOCK BULKHEAD SYSTEM

Location:

~

Type/Brand:

KEY-LOCK Bulkhead System

FRR:

~

Acoustic Mounts:

~

Curved radius:

~

Delete areas not applicable.  Add extra rows if necessary.

Refer to plasterboard manufacturers fire rated system documentation for required suspended ceiling system material and sizing requirements.

Materials - Rondo XPRESS® Drywall Grid System

Refer to Rondo for design assistance and advice.  The systems ceiling components can also be used to construct bulkheads.  This system is compatible with Rondo DONN® Exposed Grid Ceiling System.  Refer to:

5311RT RONDO SYSTEMS - TILE CEILINGS for the supply and installation of Rondo DONN® Exposed Grid Ceiling System

4.11
RONDO XPRESS® DRYWALL GRID SYSTEM

Location:

~

Type/Brand:

Rondo XPRESS ® Drywall Grid System

Grid configuration:

~

Main Tee:

~

Cross Tee:

~

Wall Trim:

~

Clips:

~

Suspension:

~

Direct fix brackets:

~

Control joints:

~

Expansion Joints:

~

Refer to Rondo for design (including seismic design) assistance and advice. This system is compatible with Rondo XPRESS® Drywall Grid Ceiling System.

Grid configuration:

Refer to grid configurations & load tables

Main Tee:

XD1 - 38mm (h) x 38mm (face) Main Tee

 

XD1H - 38mm (h) x 38mm (face) Heavy Gauge Main Tee

 

XD3 - 38mm (h) x 24mm (face) Main Tee

 

XD3H - 38mm (h) x 24mm (face) Heavy Gauge Main Tee

 

XDWS - 38mm (h) x 24mm (face) Wall to Wall Main Tee

 

XDWH - 38mm (h) x 38mm (face) Heavy Gauge Wall to Wall Main Tee

Cross Tee:

XD2 - 38mm (h) x 38mm(face) Cross Tee

 

XD4 - 38mm (h) x 24mm (face) Cross Tee

Wall Trim:

XD5 - 40mm (h) x 40mm (w) Wall Angle

 

553 - 35mm (h) x 35mm (w) Wall Angle

 

XD6 - 40mm (h) x 38mm (w) x 19mm (w) Perimeter Channel

 

WASL - 27mm (h) x 10mm (w) x 10mm (h) x 19mm (w) Shadowline Long Leg Wall Angle

 

SA12 - 40mm (h) x 40mm (w) Wall Angle

Clips:

XDSC - Splice Clip - 180°

 

XD10 - Transition Clip - 90°

 

XD11 Acoustical Transition Clip - Rondo XPRESS® to Rondo DONN®

 

XD12 - 100mm Fascia Drywall Clip

 

XD13 - 150mm Fascia Drywall Clip

 

XD14 - 200mm Fascia Drywall Clip

 

XD16 Main Tee Separation Joint Clip

 

XD17 - Seismic Clip

 

XD19 - Strongback Clip

 

XD36 - 3-Way Off-Module Connector

Suspension:

Suspension method and position dependant on load requirements.  Rondo does not recommend mixing of suspension systems within the ceiling grid.

Direct fix brackets:

XD26 - Direct Fix Angle Bracket - 180 x 40mm

 

XD27 - Direct Fix Angle Bracket - 120 x 40mm

 

XD28 - Direct Fix Clip - 180mm Extenion Strip

 

XD29 - Direct Fix Clip - 180 x 50mm

Control joints:

Refer to manual for details

Expansion Joint:

Refer to manual for details

Components
4.12
TRIM

Location:

~

Wall trim:

~

Bulkhead trim:

321 (13mm)

Wall trim:

140, 141 with 129 furring channel, 142 with 308 furring channel

Delete areas of table not applicable.  Add extra rows if necessary.

Steel Stud Drywall Ceiling System
4.13
RONDO STEEL STUD AND TRACK CEILING SYSTEM

Location:

~

Type/Brand:

Rondo Steel Stud and Track Ceiling System

FRR:

~

Ceiling studs:

~

Wall track:

~

Bridging:

~

Fixing:

~

Ceiling Studs:

Refer to design manual.

Wall Track:

Refer to design manual.

Bridging:

Stud or track section, refer to design manual.

Fixing:

Refer to design manual.

Refer to plasterboard manufacturers fire rated system documentation for required suspended ceiling system material and sizing requirements.

Access Panels
4.14
METAL FACED ACCESS PANELS

Location:

~

Brand:

Rondo PANTHER® Access Panel Systems

Type:

Metal faced

Size:

~

Refer to Rondo Building Services Pty Ltd to confirm selection, all panels are available in custom sizes to order.

Type:

Description & dimensions

flanged - refers to metal perimeter trim

Set bead - allows for stopping to panel edge perimeter.

Metal faced MFAP FE

Slimline Metal-face door, flanged

 

300 x 300mm, 450 x 450mm, 550 x 550mm, 600 x 600mm

Metal faced MFAP SB

Slimline Metal-face door, set bead

 

300 x 300mm, 450 x 450mm, 550 x 550mm, 600 x 600mm

4.15
SOUND RATED ACCESS PANELS - Rw 30

Location:

~

Brand:

Rondo PANTHER® Access Panel Systems

Type:

Sound rated

Size:

~

Refer to Rondo Building Services Pty Ltd to confirm selection, all panels are available in custom sizes to order.

Type:

Description & dimensions

flanged - refers to metal perimeter trim

Set bead - allows for stopping to panel edge perimeter.

Sound rated SRAP FE

Sound rated, polymer frame, flanged

 

300 x 300mm, 450 x 450mm, 530 x 530mm, 600 x 600mm

Sound rated SRAP SB

Sound rated, polymer frame, set bead

 

300 x 300mm, 450 x 450mm, 530 x 530mm, 600 x 600mm

4.16
SOUND RATED ACCESS PANELS - HIGH PERFORMANCE Rw 51

Location:

~

Brand:

Rondo PANTHER® Access Panel Systems

Type:

Sound rated

Size:

~

Refer to Rondo Building Services Pty Ltd to confirm selection, all panels are available in custom sizes to order.

Type:

Description & dimensions

flanged - refers to metal perimeter trim

Set bead - allows for stopping to panel edge perimeter.

Sound rated SRAP FE

Sound rated, polymer frame, flanged

 

300 x 300mm, 450 x 450mm, 530 x 530mm, 600 x 600mm

Sound rated SRAP SB

Sound rated, polymer frame, set bead

 

300 x 300mm, 450 x 450mm, 530 x 530mm, 600 x 600mm

4.17
FIRE RATED ACCESS PANELS

Location:

~

Brand:

Rondo PANTHER® Access Panel Systems

Type:

Fire rated

Size:

~

Refer to Rondo Building Services Pty Ltd to confirm selection, suitable for suspended ceilings only, all panels are available in custom sizes to order.

Type:

Description & dimensions

flanged - refers to metal perimeter trim

Set bead - allows for stopping to panel edge perimeter.

Fire rated FRAP1H FE

1 hour fire rated - flanged

 

300 x 300mm, 450 x 450mm, 530 x 530mm, 600 x 600mm

Fire rated FRAP1H SB

1 hour fire rated - set bead

 

300 x 300mm, 450 x 450mm, 530 x 530mm, 600 x 600mm

Fire rated FRAP2H FE

2 hour fire rated - flanged

 

300 x 300mm, 450 x 450mm, 530 x 530mm, 600 x 600mm

Fire rated FRAP2H SB

2 hour fire rated - set bead

 

300 x 300mm, 450 x 450mm, 530 x 530mm, 600 x 600mm

4.18
TILE FACED ACCESS PANELS

Location:

~

Brand:

Rondo PANTHER® Access Panel Systems

Type:

Tile faced

Size:

~

Refer to Rondo Building Services Pty Ltd to confirm selection, all panels are available in custom sizes to order.

NOTE - the panel comes ready to receive tiles supplied by others to suit surrounding linings and is installed as an on-site process.

Type:

Description & dimensions

flanged - refers to metal perimeter trim

Set bead - allows for stopping to panel edge perimeter.

Special Tile Access Panel

To accommodate tiles to face. Refer to Rondo Building Services Pty Ltd to confirm selection.

4.19
WET LINE MOISTURE RESISTANT POLYMER BOARD FACED ACCESS PANEL

Location:

~

Brand:

Rondo PANTHER® Access Panel Systems

Type:

Advanced Polymer Board Panel

Size:

~

Refer to Rondo Building Services Pty Ltd to confirm selection, all panels are available in custom sizes to order.

Type:

Description & dimensions

flanged - refers to polymer or metal perimeter trim

Set bead - allows for stopping to panel edge perimeter.

Special Wetline Access Panel

Refer to Rondo Building Services Pty Ltd to confirm selection.

4.20
PERFORATED PLASTERBOARD ACCESS PANEL

Location:

~

Brand:

Rondo PANTHER® Access Panel Systems

Type:

Formed to accept Decorative Plasterboard Insert sound rated

Size:

~

Refer to Rondo Building Services Pty Ltd to confirm selection, all panels are available in custom sizes to order.

NOTE - Panel comes ready to receive board supplied by others to suit surrounding linings and is installed as an on-site process.

Type:

Description & dimensions

flanged - refers to metal perimeter trim

Set bead - allows for stopping to panel edge perimeter.

Size:

polymer frame, set bead for panel sizes.

300 x 300mm

450 x 450mm

530 x 530mm

Metal frame, set bead

600 x 600mm

Insulation & Linings
4.21
INSULATION

Location:

~

Brand:

~

Type:

~

Thickness:

~

Delete when cross referencing to other sections.

4.22
PLASTERBOARD

Location:

~

Brand:

~

Type:

~

Thickness:

~

Finish:

~

Delete when cross referencing to other sections.

4.23
LINING BOARD

Location:

~

Brand:

~

Type:

~

Thickness:

~

Finish:

~

Delete when cross referencing to other sections.

Spares & maintenance products
4.24
SPARES & MAINTENANCE PRODUCTS

Refer to the general section 1270 CONSTRUCTION for details of how spares and maintenance products will be handled.  Provide the following spares and maintenance products:

Item:

~

Quantity:

~

Location:

Refer to 1270 CONSTRUCTION

Location:

If a common storage location has not been nominated in 1270 CONSTRUCTION, or is not suitable for this item, then nominate a specific location or delivery instructions.

 

Deliver into a dry store at the site or elsewhere as directed and at agreed times.